Finish Requirements; Installation Components - Superior BR-42 Installation Instructions Manual

Standard series 42" wood burning fireplaces
Table of Contents

Advertisement

A
" marble slab set in
brick, "R" for the marble and mortar becomes:
"R"
= r x T
= 0.09 x
M
M
"R"
= r x T
= 0.20 x
M
M
The sum of all "R values" is:
.70 + .10 +. 068 + .10 = .968
This would not be an acceptable combination
of material for the hearth extension since the
total calculated "R value" of the materials used
is under the required "R value" of 2.33. An
additional layer of insulating materials must
be used.
WARNING: THE CRACK BETWEEN THE
FIREPLACE AND THE HEARTH EXTEN-
SION MUST BE SEALED WITH A NON-
COMBUSTIBLE MATERIAL.
WARNING: WHEN INSTALLING HEARTH
EXTENSION IN FRONT OF A NON-CIRCU-
LATING FIREPLACE MODEL, THE FIRE-
PLACE MUST BE RAISED IF HEIGHT OF
HEARTH EXTENSION EXCEEDS 7" ABOVE
THE BOTTOM OF FIREPLACE ( FIGURE 50 ).
7"
Max. Thickness Of Hearth Extension When
Non-Circulating Models Are On The Floor
Figure 50
WARNING: WHEN INSTALLING THE
HEARTH EXTENSION BE CAREFUL NOT
TO BLOCK THE HEAT-CIRCULATING AIR
INLET GRILL ON CIRCULATING MODELS.
WARNING: WHEN INSTALLING HEARTH
EXTENSION IN FRONT OF A CIRCULAT-
ING FIREPLACE MODEL, THE FIREPLACE
MUST BE RAISED IF HEIGHT OF HEARTH
EXTENSION EXCEEDS 2" ABOVE BOTTOM
OF FIREPLACE ( FIGURE 51 ).
18
" mortar covers the
" = .068
" = .10
5 1/2"
Max. Thickness Of Hearth Extension When
Circulating Models Are On The Floor
Figure 51
Secure the hearth extension to the floor to
prevent possible shifting.
FINISH TO YOUR TASTE
There are a wide variety of "finished looks" for
these fireplaces, from formal wall decor with
elaborate mantels to rustic wood paneling or
warm brick facings.
Only noncombustible materials like stone, tile,
brick, etc., may overlap the black front facing.
Do not extend these materials beyond the black
facing and into the firebox area. Be sure not to
interfere with the installation and operation of
glass doors or block the upper or lower grilles.
Seal all joints between the black facing and wall
surrounds to prevent air intrusion. Use non-
combustible caulking material only to seal the
black metal facing to the surround material on
the finished wall.
Combustible materials may project beyond the
sides of the fireplace opening as long as they
are kept within the shaded areas illustrated in
Figure 52 .
Combustible
Materials
Allowed In
Shaded Area
"Safe Zone"
12"
Figure 52
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
2"
Fireplace
1"
9"
45
Min. Distance To
9"
Protected Side Wall
Min. Distance To
12"
Unprotected Side Wall

INSTALLATION COMPONENTS

The following items are available for use in the
installation of this appliance.
Chimney Section
63L10
63L13
63L14
63L15
Canadian
62L92
Chimney Section
62L93
Storm Collar
63L59
Locking Band
63L60
Take Off Boot
91L04
Unit Mounted
Blower Switch Kit
91L48
Shipping Weight
FTF8-12
FTF8-18
FTF8-36
FTF8-48
FTF8-18C
FTF8-36C
FSC
FLB
FATO
FUBSK
188 lbs.