4 Configuration and Project Engineering

"pnetd1.cfg" gateway file

4.4.6
The PROFINET device settings are made in the "pnetd1.cfg" configuration file.
When configuring, make sure that the STEP 7 configuration and the gateway's
configuration file match exactly.
Table 4-8: Structure of the "pnetd1.cfg" gateway file
No.
Description
1.
The device configuration of the
gateway can be found in STEP 7
(TIA Portal).
2.
In the pnetd1.cfg configuration file,
the device configuration of the
gateway is programmed line by line
according to the device
configuration in STEP 7 (TIA Portal).
Each device is referred to as a
module (Mod001, Mod002,..).
For an example of how to
parameterize each module type,
please refer to the "pnetd1.cfg" file.
Note
When configuring, please note the following:
All modules following "Mod001" must be numbered consecutively and
without gaps.
Upper limit: 60 modules ("Mod060")
The configuration is not applied until a power cycle (turn off and back on) of
the gateway is complete.
Communication with S7 CPU via KNX Gateway
Entry ID: 109739689,
V1.0,
Mod001 = ID:0x16
Mod002 = ID:0x26
06/2017
Comment
IN:32
OUT:0
#INPUT_32B
IN:0
OUT:32
#OUTPUT_32B