Carrier AquaSnap 61WG Series Installation, Operation And Maintenance Instructions page 71

Water-cooled/condenserless liquid chillers/water-sourced heat pumps with or without integrated hydraulic module
Hide thumbs Also See for AquaSnap 61WG Series:
Table of Contents

Advertisement

22 - START-UP CKECKLIST FOR UNITS (USE FOR JOB FILE)
WARNING: Do not start unit if voltage imbalance is greater than 2%. Contact local power company for assistance.
All incoming power voltage is within rated voltage range
Check cooler water loop
Water loop volume = ................................................................... (litres)
Calculated volume = ................................................................... (litres)
Proper loop volume established
Proper loop corrosion inhibitor included .................................. litres of ..................................
Proper loop freeze protection included (if required) .................................. litres of ..................................
Piping includes electric heater tape, if exposed to the outside
Inlet piping to cooler includes a 20 mesh strainer with a mesh size of 1.2 mm (unit without pump)
Check pressure drop across the evaporator
Entering evaporator = .................................. (kPa)
Leaving evaporator = .................................. (kPa)
(Leaving - entering) = .................................. (kPa)
WARNING: Calculate the cooler pressure drop in performance data table (in the product data literature) to determine total
litres per second (l/s) and find unit's minimum flow rate.
Total l/s = ..................................
l/s / nominal kW = ..................................
 Total l/s is greater than unit's minimum flow rate
 Total l/s meets job specified requirement of 
Perform TEST function (indicate positive result):
warning: Once power is supplied to the unit, check the display for any alarms, such as phase reversal. Follow the TEST
function instructions in the Controls and Troubleshooting literature (follow the procedure in the Controls IOM).
Be sure that all service valves are open, before beginning the compressor test section.
To start the unit
warning: Be sure that all service valves are open, and all pumps are on before attempting to start this machine. Once all
checks have been made, move the switch to "LOCAL" or "REMOTE" from "OFF".
Unit starts and operates properly
Temperatures and pressures
WARNING: Once the machine has been operating for a while and the temperatures and pressures have stabilized, record the
following:
Evaporator EWT ..........................................................................
Evaporator LWT ...........................................................................
Suction pressure, circuit A ............................................................
Discharge pressure, cicuit A .........................................................
Suction temperature, circuit A ......................................................
Discharge temperature, circuit A ..................................................
Liquid line temperature, circuit A ..................................................
Compressor oil pressure A1(2)......................................................
Compressor oil pressure A2(2)......................................................
(1) if available and installed
(2) if installed
NOTES:
.................................................................................................................................................................................................................
.................................................................................................................................................................................................................
(l/s)
Ambient temperature ....................................................................
Condenser EWT ..........................................................................
Condenser LWT ...........................................................................
Suction pressure, circuit B(1) .......................................................
Discharge pressure, cicuit B(1) ....................................................
Suction temperature, circuit B(1)..................................................
Discharge temperature, circuit B(1)
Liquid line temperature, circuit B(1) .............................................
Compressor oil pressure B1(2) ...................................................
Compressor oil pressure B2(2)....................................................
71