Nominal Water Flow Control With Fixed-Speed Pump; General; Water Flow Control Procedure - Carrier AquaSnap 61WG Series Installation, Operation And Maintenance Instructions

Water-cooled/condenserless liquid chillers/water-sourced heat pumps with or without integrated hydraulic module
Hide thumbs Also See for AquaSnap 61WG Series:
Table of Contents

Advertisement

10 - NOMINAL WATER FLOW CONTROL WITH FIXED-SPEED PUMP

10.1 - General

The water circulation pumps of the units have been sized to allow
the hydraulic modules to cover all possible configurations based 
on the specific installation conditions, i.e.  for various temperature 
differences between the entering and the leaving water (∆T) at full 
load, which can vary between 2.5 and 7 K for evaporators and 3
and 18 K for condensers.
This required difference between the entering and leaving water
temperature determines the nominal system flow rate. It is above 
all absolutely necessary to know the nominal system flow rate to 
allow its control via a manual valve.
Manual control valves for the unit are not supplied and must be
installed upstream and downstream of the evaporator and
condenser water loops to ensure correct flow control. 
With the pressure loss generated by the control valve in the
hydraulic system, the valve is able to impose the system pressure/
flow curve on the pump pressure/flow curve, to obtain the desired 
operating point (see example).
The pressure drop reading in the plate heat exchanger is used to
control  and  adjust  the  nominal  system  flow  rate.  The  pressure 
drop is measured with the pressure sensors connected to the heat
exchanger water inlet and outlet.
Use this specification for the unit selection  to know the system 
operating conditions and to deduce the nominal air flow as well 
as the plate heat exchanger pressure drop at the specified
conditions. If this information is not available at the system start-
up, contact the technical service department responsible for the
installation to get it.
These characteristics can be obtained from the technical literature
using the unit performance tables or the Electronic Catalogue
selection program for all conditions.

10.2 - Water flow control procedure

As the total system pressure drop is not known exactly at the
start-up, the water flow rate must be adjusted with the control valve 
to obtain the specific flow rate for this application.
Proceed as follows:
- Open the valve fully.
- Start-up the pump using the forced start command (refer to
the controls manual) and let the pump run for two consecutive
hours to clean the hydraulic circuit of the system (presence
of solid contaminants).
- Read the hydraulic module pressure drop by taking the
difference of the readings at the machine connected to the
hydraulic module inlet and outlet. Compare this value after
two hours of operation.
Entering water pressure reading
F
Leaving water pressure reading
O
Legend
O
Open
F
Closed
Water inlet
Water outlet
Pressure gauge
If the pressure drop has increased, this indicates that the screen
filter  must  be  removed  and  cleaned,  as  the  hydraulic  circuit 
contains solid particles. In this case, in units with option 293 or
293A, close the shutoff valves at the water inlet and outlet and
remove the screen filter after emptying the hydraulic section of 
the unit. In units without option 293 or 293A, clean the screen filter 
on hydraulic circuit out of the unit.
Renew, if necessary, to ensure that the filter is not contaminated.
When the circuit is cleaned, read the pressures at the unit (entering
water pressure - leaving water pressure), expressed in kPa to find 
out the plate heat exchanger pressure drop.
Compare the value obtained with the theoretical selection value.
If the pressure drop measured is higher than the value specified 
this means that the flow rate in the plate heat exchanger (and thus 
in the system) is too high. The pump supplies an excessive flow 
rate based on the global pressure drop of the application. In this
case close the control valve one turn and read the new pressure
difference.
Proceed by successively closing the control valve until you obtain
the specific pressure drop that corresponds to the nominal flow 
rate at the required unit operating point.
If the system has an excessive pressure drop in relation to the
available static pressure provided by the pump, the resulting water
flow rate will be reduced and the difference between entering and 
leaving water temperature of the hydraulic module will be
increased.
O
F
F
F
49

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aquasnap 30wg seriesAquasnap 30wga series

Table of Contents