4.2
Mounting the NCS to a rotary actuator up to 14 mm (0.55 inch)
Prerequisites
1. An EMC filter module in the positioner.
2. An NCS for rotary actuators up to 14 mm (0.55 inch) 6DR4004-.N.20.
3. Linear actuator with interface to NAMUR. This installation must be carried out individually. Only a NAMUR mounting
bracket can be used as mounting base. The following figure shows the assembly with NAMUR mounting bracket.
Or
linear actuator without interface to NAMUR and individual mounting solution.
Description
Dimensions in mm
A
Mounting on a yoke with fin
B
Mounting on a yoke with plane surface
C
Mounting on a yoke with columns
NAMUR mounting bracket IEC 60534 - not
included in the scope of delivery
Figure 4-2
Example of the assembly on a linear actuator with a stroke up up to 14 mm (0.55 inch)
Procedure
1. Produce the mounting panel
2. Align the sensor to the center of the stroke. Observe the dimensions specified in the figure.
SIPART PS2 Non-Contacting Sensor (NCS)
A5E00097485-07, 01/2012
and mounting bracket
Assembly panel for Non Contacting Sensor (NCS) -
individual solution; not included in the scope of delivery
Non-contacting sensor (NCS)
Magnet
Mounting bracket for the magnet - individual solution;
not included in the scope of delivery
individually.