Configuration of DIP Switch (U3 Chassis, 2
Fan Model)
SW01B
SW02B
1
2
l 5
Short Pipe Length
5 l
Long Pipe Length
l l
Refrigerant Auto Charging
l l
Refrigerant Checking
Cool/Heat Selector
Snow (Heat Pump model)
Forced Defrosting (Heat Pump model)
Snow + Forced Defrosting (Heat Pump model)
Night Silent Operation
Pump Down
Pump Out (Heat Pump model)
5 5
Forced Oil Return
Vacuum Mode
CAUTION
!
• "X" mark means DIP switch must be off, Otherwise the function
may not perates correctly.
• If each DIP switch doesn't set correctly, unit will operate abnor-
mally.
• In case of proceeding test run, start after checking if all indoor unit
is off.
Location of DIP Switch (U4 Chassis, 1 Fan
Model)
Main PCB
SW01N
<Initial shipping condition of DIP Switch>
WARNING
!
• Main PCB power should be reset in order to recognize the changed
function after handling the DIP switch for configuration of additional
functions.
• Main PCB power should be reset after resetting the DIP switch for
cancellation of additional function
• Please configure DIP switch properly. Otherwise, It can overstrain
product during operation
3
4
5
6
7
8
9
10 11 12 13 14
l
l
l l 5
5 l 5
5 5 l
5 l l
l
l
l
l
l
SW01N
LED01M (Red)
LED02M (Green)
SW02N
Auto Addressing
Configuration of DIP Switch (U4 Chassis, 1 Fan
Model)
SW01N
Short Pipe Length
Long Pipe Length
Cool/Heat Selector
l
Forced Oil Return
Forced Defrosting
Vacuum Mode
Pump Down
Pump Out
l
Night Silent Operation Step 1
5
Night Silent Operation Step 2
l
Night Silent Operation Step 3
l
Automatic Addressing (U3 Chassis, 2 Fan
Model)
The address of indoor units would be set by auto addressing
- Wait for 3 minutes after applying power supply
(outdoor unit, indoor unit).
- Press the switch of the outdoor unit (SW02V) for 5 seconds.
- A "88" is indicated on 7-segment LED of the outdoor unit PCB.
- For completing addressing, 2~7 minutes are required depending on
numbers of indoor unit connection set.
- Numbers of indoor unit connection set whose addressing is com-
pleted are indicated for 30seconds on 7-segment LED of the outdoor
unit PCB.
- After completing addressing, address of each indoor unit is indicated
on the wired remote control display window. (CH01, CH02,
CH03, ............. CH06: Indicated as numbers of indoor unit connection
set.)
SW02V
Auto addressing
7 - Segment
SW02B
(DIP S/W)
SW01B
(DIP S/W)
CAUTION
!
In replacement of the indoor unit PCB, always perform auto address
setting again.
- If power supply is not applied to the indoor unit, operation error oc-
curs.
- Auto addressing is only possible on the main PCB
- Auto addressing has to be performed after 3 minutes to improve
communication.
1
2
3
4
l
l
l
l
l
l
l
l
SW01V
Data confirm
23
5
6
l
l
l
l
l
l
l
l