Siemens SITRANS T3K PA Instruction Manual page 74

Table of Contents

Advertisement

Available languages

Available languages

7NG3213
Reference point compensa-
tion
Measuring range
Characteristic
Millivolt transmitter
Sensor type
Standard
Input range
Overloadability of the input
Characteristic
Input resistance
Sensor current
Measuring accuracy
Reference conditions
Power Supply
Ambient temperature
Warming-up time
Measuring error
Error in the internal refe-
rence point
Temperature drift
74
Type specification
D No compensation (2 channels)
D Internal acquisition with integrated or with
external sensor: for the "external sensor"
case a manufacturer-specific PA-parameter
must be set (default value: internal sensor);
see chapter 3.8, page 91.
D Externally specified reference point tem-
perature can be set as a fixed value
Depending on connected sensor type
Temperature linear
Linear
1 millivolt transmitter (logic channel 1)
7 voltage ranges selectable:
–1 to 16 mV
–3 to 32 mV
–7 to 65 mV
–15 to 131 mV
–31 to 262 mV
–63 to 525 mV
–120 to 1000 mV
max. 3.5 V
Voltage linear
≥1 MΩ
180 μA
15 V 1 %
23 °C
1 h
See Table 4, page 77
<0.5 _C 0.1 %/10 °C
± 0.05 %/10 °C FSR,
0.1 % in the range from –10 °C to 60 °C
Instruction Manual
SITRANS T3K PA
C79000-B7174-C55-04