Status - Siemens SITRANS T3K PA Instruction Manual

Table of Contents

Advertisement

Available languages

Available languages

Instruction Manual
1.3.3

Status

The status provides information about the quality of the measured value (data
according to PROFIBUS--PA General Requirements, see appendix 3, page 117
"Literature and Catalogs" /10/) and has the following structure:
7
6
Quality
D Quality (bits 6 and 7), global information about order:
0 =
Poor
1 =
Uncertain
2 =
Good
3 =
Good (cascade) (not relevant for transmitters)
D Sub-status: Additional information on quality
D Limit value (bits 0 and 1)
0 =
Good
1 =
Lower limit reached, exceeded or at limited to lower limit
value. This also includes short-circuit.
2 =
Upper limit reached, exceeded or limited to upper limit
value. This also includes open circuit.
3 =
Value is fixed, no measured value
SITRANS T3K PA
C79000-B7174-C55-04
5
4
Sub-status
3
2
7NG3213
1
0
Limit value
65