Technische Daten; About This Document; General Safety Precautions - STEINEL Light Sensor Dual KNX Information

Table of Contents

Advertisement

Available languages

Available languages

9� Technische Daten
Abmessungen (L × B × H)
Aufputz rund Ø
Aufputz eckig
Unterputz rund Ø
Unterptutz eckig
Versorgungsspannung
KNX Busspannung, 21 V - 30 V
Sensorik
2 x Fotodiode
Montagehöhe
max. 4 m
Einstellungen
über ETS-Software, Fernbedienung oder BUS
Erfassungswinkel
gerichtet/diffus 2-1000 Lux
Dämmerungseinstellung
2-1000 Lux, Teach
(nur über RC 6 oder Smart Remote)
Ausgang Licht
Schalten/Dimmen
Licht 1 - Licht 2
Nachlaufzeit Beleuchtung
1 - 255 min
weitere Ausgänge
Sabotageschutz, Messwert Helligkeit
Schutzart
Aufputz: IP 54
Temperaturbereich
- 20 °C bis + 50 °C
10� Betriebsstörungen
Störung
Ursache
Sensor ohne Spannung
n Leitung
unterbrochen
Sensor schaltet nicht ein
n Glühlampe defekt
126 × 52 mm
95 × 95 × 52 mm
124 × 64 mm
94 × 94 × 64 mm
(SELV)
Unterputz: IP 20
Abhilfe
n KNX Spannungsversorgung
überprüfen
n Glühlampe
austauschen
14
GB
1� About this document
– Please read carefully and keep in a safe place.
– Under copyright.
Reproduction either in whole or in part only with our consent.
– Subject to change in the interest of technical progress.
Symbols
!
Hazard warning!
Reference to other information in the document�
...
2� General safety precautions
!
Disconnect the power supply before attempting any work on the sensor�
• This product must only be installed by a qualified electrician in accordance with
national wiring regulations as defined in VDE 08 29 (DIN EN 5000 90).
• Installed improperly, low-voltage products can cause extremely serious personal
injury or damage to property.
• This product must never be connected to a 230 V AC power supply as it is intend-
ed for connection to an extra-low voltage power supply.
• Only use genuine replacement parts.
• Repairs may only be made by specialist workshops.
3� Light Sensor Dual KNX
Proper use
– Sensor suitable for ceiling and wall mounting indoors and outdoors.
The light sensor measures ambient light level with two different lenses, directed and
diffuse. Depending on requirement, it is possible to select the brightness level trans-
mitted to the system.
Package contents for surface-mounted installation (Fig� 3�1)