Main Service - Siemens 1PL618 Series Operating Instructions Manual

Ac compact drives;
Table of Contents

Advertisement

Maintenance
7.2 Inspection
NOTICE
Adapt the inspection to the plant-specific conditions
This list does not claim to be complete.
Further tests also should be carried out in accordance with the additional instruction
manuals (e.g. bearings, cooler, etc.) or in accordance with the particular system-specific
conditions.
[ID: 367.02]
7.2.3

Main service

Inspection interval for major inspection
The main inspection is conducted after approx. 16,000 operating hours or at the latest after 2
operating years.
Conducting the major inspection
● While the motor is running, check that:
● When the motor has been shut down, check that:
[ID: 368]
56
– the equipment conforms to the stated electrical characteristics.
– the smooth running characteristics and motor noise during operation have not
deteriorated.
– the motor foundation has no indentations or cracks.
– the motor is aligned within the permissible tolerance ranges.
– all of the fixing bolts for the mechanical and electrical connections are tight.
– The winding isolation resistances are sufficiently high.
– cables and insulating parts and components are in a good condition and are not
discolored.
NOTICE
Any inadmissible deviations from these requirements detected during this inspection
must be rectified immediately.
Siemens AG Operating Instructions 2.02 1PL618
A5E00215731A AD

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1pl61841pl6186

Table of Contents