Carrier WeatherMaster 48HC04 Service And Maintenance Instructions page 93

Single package rooftop gas heat/electric cooling unit with puron (r-410a) refrigerant
Hide thumbs Also See for WeatherMaster 48HC04:
Table of Contents

Advertisement

Table AH — 48HC**14 3 Phase, 12.5 Ton, Vertical Supply — Belt Drive Fan Performance
CFM
0.2
RPM
3438
431
3750
456
4063
481
4375
507
4688
533
5000
560
5313
587
5625
614
5938
642
6250
670
CFM
1.2
RPM
3438
763
3750
772
4063
781
4375
790
4688
801
5000
814
5313
830
5625
847
5938
865
6250
885
NOTES:
1. For more information, see fan performance notes on page 93.
2. Boldface indicates field-supplied drive is required.
Standard static 440-609 RPM, 2.9 bhp max
Medium static 609-778 RPM, 3.7 bhp max
High static 776-955 RPM
Voltage: 208-v / 230-v / 460-v / 575-v
Max bhp: 6.5 /
6.9 / 7.0 / 8.3
FAN PERFORMANCE NOTES:
1.
Interpolation is permissible. Do not extrapolate.
2.
External static pressure is the static pressure difference between the return duct and the supply duct plus the static pressure
caused by any FIOPs or accessories.
3.
Tabular data accounts for pressure loss due to clean filters, unit casing, and wet coils. Factory options and accessories may add
static pressure losses. Selection software is available, through your salesperson, to help you select the best motor/drive combina-
tion for your application.
4.
The fan performance tables offer motor/drive recommendations. In cases when two motor/drive combinations would work,
Carrier recommends the lower horsepower option.
5.
For information on the electrical properties of Carrier motors, please see the Electrical Data section of this unit's product data.
6.
For more information on the performance limits of Carrier motors, see the application data section of this unit's product data.
7.
The EPACT (Energy Policy Act of 1992) regulates energy requirements for specific types of indoor fan motors. Motors regu-
lated by EPACT include any general purpose, T-frame (three-digit, 143 and larger), single-speed, foot mounted, polyphase,
squirrel cage induction motors of NEMA (National Electrical Manufacturers Association) design A and B, manufactured for use
in the United States. Ranging from 1 to 200 Hp, these continuous-duty motors operate on 230 and 460 volt, 60 Hz power. If a
motor does not fit into these specifications, the motor does not have to be replaced by an EPACT compliant energy-efficient
motor. Variable-speed motors are exempt from EPACT compliance requirements.
APPENDIX C — FAN PERFORMANCE
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.4
BHP
RPM
BHP
0.59
504
0.81
0.71
524
0.95
0.86
546
1.11
1.03
569
1.30
1.22
593
1.51
1.44
617
1.74
1.68
642
2.00
1.95
667
2.29
2.25
692
2.60
2.58
718
2.95
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.4
BHP
RPM
BHP
2.10
815
2.46
2.28
825
2.66
2.46
834
2.87
2.66
843
3.09
2.89
852
3.32
3.15
863
3.58
3.44
875
3.87
3.77
890
4.20
4.13
906
4.56
4.53
924
4.97
0.6
RPM
BHP
RPM
574
1.08
643
589
1.22
653
606
1.39
666
626
1.59
681
647
1.81
698
669
2.05
718
691
2.33
738
715
2.63
760
739
2.97
782
763
3.33
805
1.6
RPM
BHP
RPM
862
2.82
905
873
3.05
918
883
3.29
929
892
3.53
938
901
3.78
947
910
4.04
956
920
4.33
965
933
4.66
975
947
5.03
987
962
5.43
1001
93
0.8
1.0
BHP
RPM
1.40
706
1.54
715
1.71
725
1.91
736
2.13
750
2.39
766
2.67
784
2.99
804
3.34
824
3.72
846
1.8
2.0
BHP
RPM
3.18
946
3.45
959
3.71
971
3.98
982
4.25
991
4.53
999
4.83
1008
5.15
1017
5.52
1028
5.92
BHP
1.74
1.90
2.07
2.27
2.49
2.75
3.04
3.36
3.72
4.11
BHP
3.55
3.84
4.14
4.43
4.73
5.03
5.34
5.67
6.04