Carrier WeatherMaster 48HC04 Service And Maintenance Instructions page 16

Single package rooftop gas heat/electric cooling unit with puron (r-410a) refrigerant
Hide thumbs Also See for WeatherMaster 48HC04:
Table of Contents

Advertisement

CHARGING CHART – R-410A REFRIGERANT
COOLING MODE – OUTDOOR FAN MUST BE RUNNING
160
140
120
Add charge if above the curve
100
80
60
Remove charge if below the curve
40
20
150
200
250
300
350
Compressor Discharge Pressure (psig)
Fig. 23 — Cooling Charging Chart - 5 Ton
CHARGING CHART – R-410A REFRIGERANT
COOLING MODE – ALL OUTDOOR FANS MUST BE RUNNING
160
140
120
Add charge if above the curve
100
80
60
Remove charge if below the curve
40
20
150
350
200
250
300
Compressor Discharge Pressure (psig)
Fig. 24 — Cooling Charging Chart - 6 Ton
550
400
450
500
600
REV C
48TM502522
400
500
450
550
600
48TM502680
REV B
2-Stage 6 Ton Charging Chart R-410A Refrigerant
(Cooling Mode - Compressor at Full Load
and Outdoor Fans at High Speed)
60
140
54
120
48
Add Charge if
42
Above the Curve
100
36
30
80
24
18
60
12
6
40
0
-6
20
50
100
150
200
350
700
1050 1400 1750 2100 2450 2800 3150 3500 3850
Compressor Discharge Pressure (PSIG / Kpa)
Fig. 25 — Cooling Charging Chart - 2 Stage 6 Ton
CHARGING CHART – R-410A REFRIGERANT
COOLING MODE – ALL OUTDOOR FANS MUST BE RUNNING
160
140
Add charge if above the curve
120
100
80
60
40
20
150
200
250
300
Compressor Discharge Pressure (psig)
Fig. 26 — Cooling Charging Chart - 7.5 Ton
16
Remove Charge if
Below the Curve
250
300
350
400
450
500
550
600
48TM002738
Remove charge if below the curve
350
400
450
500
550
48TM502681
REV-
600
REV B

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents