... External position sensors
Note
To connect the EDP300 Remote Sensor, a cable with the
following specifications needs to be used:
3-wire, cross-section 0.5 to 1.0 mm²
shielded, with at least 85 % coverage
Temperature range up to at least 100 °C (212 °F)
The cable glands must also be approved for a temperature range
up to at least 100 °C (212 °F). The cable glands require a
mounting for the shielding and strain relief for the cable in
addition.
ABB optionally offers a cable gland and cable for the EDP300
Remote Version.
EDP300 Control Unit for remote position sensor
B
In this version the positioner is supplied without a position
sensor.
The following points should be observed during installation:
Housing 1 (EDP300 Control Unit) contains the electronics
and pneumatics and is mounted separately from the
actuator.
The remote position sensor is mounted on the linear
actuator or rotary actuator. Follow the operating
instructions for the remote position sensor for

mechanical mounting!

Electrical connection is carried out as described in
Connection to device - EDP300 Control Unit for remote
position sensor on page 31.
Mechanical mounting

General

Figure 3: Operating range
Arrow
on the device feedback shaft (position feedback point)
1
must move between the arrow marks
1
+45°
2
-45°
1 Measuring range
Figure 4: Measuring and operating ranges of the positioner
1
2
M10408-01
.
2
+135°
-135°
M11103
2 Operating range