TZIDC DIGITAL POSITIONER | CI/TZIDC/C-FM-US-EN REV. A
... 5 Installation
... External position sensors
TZIDC Control Unit with TZIDC Remote Sensor*
A
In this version, the components are supplied in two housings,
which together form one harmonized unit.
The following points should be observed during installation:
•
Housing 1 (TZIDC Control Unit) contains the electronics
and pneumatics and is mounted separately from the
actuator.
•
Housing 2 (TZIDC Remote Sensor) contains the position
sensor and is mounted on the linear and rotary actuator.
Perform mechanical mounting as described in Mechanical
mounting on page 18.
•
The electrical connection is performed as described in
Connection on device - TZIDC Control Unit with TZIDC
Remote Sensor on page 30.
Note
To connect the TZIDC Remote Sensor, a cable with the following
specifications needs to be used:
•
3-wire, cross-section 0.5 to 1.0 mm
•
shielded, with at least 85 % coverage
•
Temperature range up to at least 100 °C (212 °F)
The cable glands must also be approved for a temperature range
up to at least 100 °C (212 °F). The cable glands require a
mounting for the shielding and strain relief for the cable in
addition.
*
The TZIDC Remote Version is temporarily not available for the marine
version.
B TZIDC Control Unit for remote position sensor
In this version the positioner is supplied without a position
sensor.
The following points should be observed during installation:
•
Housing 1 (TZIDC Control Unit) contains the electronics
and pneumatics and is mounted separately from the
actuator.
•
The remote position sensor is mounted on the linear and
rotary actuator. Follow the operating instructions for the
remote position sensor for mechanical mounting!
•
The electrical connection is performed as described in
Connection on device - TZIDC Control Unit for remote
position sensor on page 31.
Mechanical mounting
General
Figure 3: Operating range
2
Arrow
must move between the arrow marks
1 Measuring range
2 Operating range
Figure 4: Measuring and operating ranges of the positioner
1
on the device feedback shaft (position feedback point)
A The position of the ventilation
2
.
must be selected so that the IP
rating of the housing is not
impaired.