9 Maintenance

The positioner does not require any maintenance if it is used as
intended under normal operating conditions.
Note
Manipulation by users shall immediately render the warranty for
the device invalid.
To ensure fault-free operation, it is essential that the device is
supplied with instrument air that is free of oil, water, and dust.
Note
Perform a functional check of the emergency shutdown module
(option) at least every 2 years.
For this purpose, the positioner must move the valve into the
safety position when the 24 V DC signal (terminal +85 / −86) is
interrupted.

10 Recycling and disposal

Note
Products that are marked with the adjacent symbol
may not be disposed of as unsorted municipal waste
(domestic waste).
They should be disposed of through separate
collection of electric and electronic devices.
This product and its packaging are manufactured from materials
that can be recycled by specialist recycling companies.
Bear the following points in mind when disposing of them:
As of 8/15/2018, this product will be under the open
scope of the WEEE Directive 2012/19/EU and relevant
national laws (for example, ElektroG - Electrical
Equipment Act - in Germany).
The product must be supplied to a specialist recycling
company. Do not use municipal waste collection points.
These may be used for privately used products only in
accordance with WEEE Directive 2012/19/EU.
If there is no possibility to dispose of the old equipment
properly, our Service can take care of its pick-up and
disposal for a fee.

11 Supplemental specifications

Actuator travel

Rotation angle
Used range
25 to 270° for rotary actuator
25 to 60° for linear actuator
Actuator travel limit
Min. and max. limits, freely configurable in
range 0 to 100 %
Actuator travel (min. range > 20%
Actuator travel time
Range of 0 to 200 seconds, separately for each
prolongation
direction
Dead band time limit
Setting range 0 to 200 seconds
(monitoring parameter for control until the
deviation reaches the dead band)

Housing

Material / Degree of protection
Aluminum with ≤ 0.1% copper Optional stainless steel 1.4404 (316L)
Degree of protection
IP 65 / NEMA 4X (NEMA 4X does not permit
overhead mounting)
Surface / color (aluminum housing only)
Dipping varnish
With epoxy resin, stove-hardened
Housing varnished black
RAL 9005
RAL 9002
Weight
Aluminum
Stainless steel 1.4404 (316L)
Mounting orientation
Any
41
2.4 kg (5.29 lb)
5.5 kg (12.13 lb)