Precautions For Correct Use - Omron G3PE Series Manual

Single-phase solid state relays for heaters
Hide thumbs Also See for G3PE Series:
Table of Contents

Advertisement

Precautions for Correct Use

The SSR in operation may cause an unexpected accident.
Therefore it is necessary to test the SSR under the variety of
conditions that are possible. As for the characteristics of the SSR, it is
necessary to consider differences in characteristics between
individual SSRs.
The ratings in this catalog are tested values in a temperature range
between 15°C and 30°C, a relative humidity range between 25% and
85%, and an atmospheric pressure range between 86 and 106 kPa.
It will be necessary to provide the above conditions as well as the load
conditions if the user wants to confirm the ratings of specific SSRs.
Causes of Failure
• Do not drop the G3PE or subject it to abnormal vibration or shock
during transportation or mounting. Doing so may result in
deterioration of performance, malfunction, or failure.
• Tighten each terminal to the torque specified below. Improper
tightening may result in abnormal heat generation at the terminal,
which may cause burning.
Terminals
Screw terminal diameter
Input terminals
M3.5
Output
M4
terminals
M5
• Do not supply overvoltage to the input circuits or output circuits.
Doing so may result in failure or burning.
• Do not use or store the G3PE in the following conditions. Doing so
may result in deterioration of performance.
• Locations subject to static electricity or noise
• Locations subject to strong electric or magnetic fields
• Locations subject to radioactivity
Mounting
• The G3PE is heavy. Firmly mount the DIN Track and secure both
ends with End Plates for DIN Track mounting models. When
mounting the G3PE directly to a panel, firmly secure it to the panel.
Screw diameter:
M4
Tightening torque: 0.98 to 1.47 N·m
Mounted on a
vertical surface
Vertical
Direction
Panel
Note: Make sure that the load current is 50% of the rated load current
when the G3PE is mounted horizontally.
For details on close mounting, refer to the related information
under performance characteristics.
Mount the G3PE in a direction so that the markings read natu-
rally.
Wiring
• When using crimp terminals, refer to the terminal clearances
Output Terminal Section for Three-phase Models
Output Terminal Section for Single-phase Models
Tightening torque
Input Terminal Section
0.59 to 1.18 N·m
0.98 to 1.47 N·m
1.57 to 2.45 N·m
• Make sure that all lead wires are thick enough for the current.
• For three-element and two-element models, the output terminal will
• Terminal L2 and terminal T2 of a 2-element model are internally
Fuses
Mounted on a
horizontal surface
• Use a quick-burning fuse on the output terminals to prevent
Recommended Fuse Capacity
Panel
Rated G3PE output
Single-phase Solid State Relays for Heaters
shown below.
7 mm
15-A and 25-A Models
10 mm
12.4 mm
M4 (15 A, 25 A)
be charged even when the Relay is OFF. Touching the terminal
may result in electric shock. To isolate the Relay from the power
supply, install an appropriate circuit breaker between the power
supply and the Relay.
Always turn OFF the power supply before wiring the Unit.
connected to each other. Connect terminal L2 to the ground
terminal of the power supply.
If terminal L2 is connected to a terminal other than the ground
terminal, cover all the charged terminals, such as heater terminals,
to prevent electric shock and ground faults.
accidents due to short-circuiting. Use a fuse with equal or greater
performance than those given in the following table.
Applicable SSR
current
15 A
G3PE@15B Series
25 A
G3PE@25B Series
35 A
G3PE@35B Series
45 A
G3PE@45B Series
13 mm
12 mm
M4 (15 A, 25 A)
M5 (35 A, 45 A)
35-A and 45-A Models
13 mm
12.9 mm
M5 (35 A, 45 A)
7.0 mm
10 mm
M3.5
Fuse
(IEC 60269-4)
32 A
63 A
G3PE
451