Installation of a EVO-COOL® in a Viessmann coldroom
Sufficient free space must be provided for the intake and
discharge openings on the left side of the refrigeration
unit in order to warrant a good air flow:
- at least 250 mm from all ventilation openings.
A wall element can be delivered by us with the respec-
tive cut-outs and bore holes for installation in the cold
storage cell.
Otherwise, the required bores holes and cut-outs
should be made on location by a refrigeration techni-
cian using installation templates or the dimensional
drawings.
The cutting edges and bore holes must be protected
against corrosion with zinc primer paint.
Attention!
The electrical power supply should first be connected
at commissioning after installation has been com-
pleted - Risk of life!
Loosen the holding angle from the unit.
To prevent ice formation and not restrict access for
servicing, should be maintained between the
coldroom wall and the evaporator, a minimum
distance of 50 or 100 mm.
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or
regarding a certain purpose always require a special written agreement.
Page 42 GB
Installation template
> 50 mm
Right reserved to make technical changes!
> 100 mm