G3PE
Precautions for Correct Use
The SSR in operation may cause an unexpected accident.
Therefore it is necessary to test the SSR under the variety of
conditions that are possible. As for the characteristics of the SSR, it is
necessary to consider differences in characteristics between
individual SSRs.
The ratings in this catalog are tested values in a temperature range
between 15°C and 30°C, a relative humidity range between 25% and
85%, and an atmospheric pressure range between 86 and 106 kPa.
It will be necessary to provide the above conditions as well as the load
conditions if the user wants to confirm the ratings of specific SSRs.
Causes of Failure
• Do not drop the G3PE or subject it to abnormal vibration or shock
during transportation or mounting. Doing so may result in
deterioration of performance, malfunction, or failure.
• Tighten each terminal to the torque specified below. Improper
tightening may result in abnormal heat generation at the terminal,
which may cause burning.
Terminals
Screw terminal diameter
Input terminals
Output
terminals
• Do not supply overvoltage to the input circuits or output circuits.
Doing so may result in failure or burning.
• Do not use or store the G3PE in the following conditions. Doing so
may result in deterioration of performance.
• Locations subject to static electricity or noise
• Locations subject to strong electric or magnetic fields
• Locations subject to radioactivity
Mounting
The G3PE is heavy. Firmly mount the DIN track and secure both ends
with End Plates for DIN-track-mounting models. When mounting the
G3PE directly to a panel, firmly secure it to the panel.
Mounted on a
vertical surface
Vertical
Direction
Panel
Note: Make sure that the load current is 50% of the rated load current
when the G3PE is mounted horizontally.
For details on close mounting, refer to the related information
under performance characteristics.
Mount the G3PE in a direction so that the markings read
naturally.
When close-mounting G3PE SSRs, check Load Current vs.
Ambient Temperature under Engineering Data on page 3.
6
Tightening torque
M3.5
0.59 to 1.18 N·m
M4
0.98 to 1.47 N·m
M5
1.57 to 2.45 N·m
Mounted on a
horizontal surface
Panel
Wiring
• When using crimp terminals, refer to the terminal clearances
shown below.
Output Terminal Section
15-A and 25-A Models
10 mm
12.4 mm
M4 (15 A, 25 A)
Output Terminal Section
• Make sure that all lead wires are thick enough for the current.
Fuses
• Use a quick-burning fuse on the output terminals to prevent
accidents due to short-circuiting. Use a fuse with equal or greater
performance than those given in the following table.
Recommended Fuse Capacity
Rated G3PE output
Applicable SSR
current
15 A
G3PE@15B Series
25 A
G3PE@25B Series
35 A
G3PE@35B Series
45 A
G3PE@45B Series
EMC Connection
Make EMC connections according to the following figure.
• Connect a capacitor to the load power supply.
• The input cable must be no longer than 3 m.
G3PE
Input
3 m max.
Recommended Capacitor (Film Capacitor)
G3PE-2@@B Series: 1 µ F, 250 VAC
G3PE-5@@B Series: 0.5 µ F, 500 VAC
EMI
This is a Class A product (for industrial environments). In a domestic
environment, the G3PE may cause radio interference, in which case
the user may be required to take appropriate measures.
35-A and 45-A Models
13 mm
12.9 mm
M5 (35 A, 45 A)
7.0 mm
10 mm
M3.5
Fuse
(IEC 60269-4)
32 A
63 A
Load
Output