Unpowered Convenience Outlet Unpowered Option (Fiycoup); 10 Tons - Trane Axiom GWS Series Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

Unpowered Convenience Outlet
Unpowered Option (FIYCOUP)
1. When the unpowered convenience outlet option is
installed, remove the receptacle.
2. The field wiring should be routed through the hole
in the base for downflow applications or front panel
for horizontal applications then through holes
provided in the "J" box (bottom for EMT and top
for flexible conduit).
3. Connect the three (3) wires to terminals inside
outlet box.
Figure 51. Power options
A - Powered
B - Powered
Return Air Smoke Detector 3 to

10 Tons

The factory installed Return Air Smoke Detector is
installed in the downflow discharge position. No
additional field setup is required.
If a unit is to be converted to Horizontal discharge, the
following conversion must be performed:
1. If the unit has an economizer, it must be pulled out
in the operating position.
2. Remove the 3 screws from the mounting brackets.
Refer to downflow view for screw locations.
N N o o t t e e : : Refer to downflow view for screw locations.
WSHP-SVX015C-EN
F F a a c c t t o o r r y y - - M M o o u u n n t t e e d d U U n n i i t t O O p p t t i i o o n n s s
Figure 52. Downflow view
3. Lift the tube and bracket from the downflow duct
opening. Rotate the tube and bracket assembly 180°
degrees ensuring that the holes on the copper
sensing tube face away from the unit and face the
return air ductwork.
N N o o t t e e : : Refer to horizontal views below.
N N o o t t e e : : Check to insure that the flexible tubing lies
flat on the base pan surface.
4. Slide the top bracket down the copper sensing tube,
insert the tab on the left side into the slot on the
indoor coil block off and secure the right side of the
bracket with one of the 3 screws removed in step 2.
N N o o t t e e : : Refer to horizontal view.
5. Using the remaining 2 screws removed in step 2,
secure the bottom bracket.
N N o o t t e e : : Refer to horizontal views below.
49