Installation of Inner Door with Gasket

Step 1.
Clean any residual gasket residue or other
debris from combustion chamber surface
before installing the inner door/gasket
assembly.
Place the left side inner door into position
Step 2.
first. Firmly position the radiused channel of
the inner door around the feedline. Using the
two (2) hex drive screws from Step 3d,
secure left side inner door in place. DO NOT
OVER TIGHTEN SCREWS.
Position thermocouple, pilot tube and piezo
Step 3.
wire against left side inner door flange gasket.
DO NOT ROUTE THROUGH RADIUSED
CHANNEL WITH FEEDLINE.
Radiused channel for
feedline
SERVICE PROCEDURE RG-I
Inner Door/Gasket Removal,
Inspection, and Replacement
Stripped fastener connections may allow
for seal breach of inner door. A seal
breach may result in a fire or explosion
causing property damage, personal injury
or death. DO NOT overtighten screws in
If a fastener connection is stripped,
contact the manufacturer listed on the
water heater rating plate.
13
WARNING
Step s 2, 4, and 5.
13