Information You Need To Give To Your Customer; Security And Application Port Numbers - Siemens DMS8000 Application & Planning

Hide thumbs Also See for DMS8000:
Table of Contents

Advertisement

NK8000 network planning
5.4.1

Information you need to give to your customer

5.4.2

Security and application port numbers

84
Building Technologies
CPS Fire Safety
Also, you will need to determine the following regarding the client's network:
· Maintenance times for the network (shutdown of the network)
· Network utilisation (Load > 30 – 40 % is bad on shared network)
· Collision rate (< 5% is good)
· Stability of the network (> 99.9% is good)
· Availability of the network (Downtime)
· Access time to the network (timeouts/access time < 1 sec. is good)
· Responsibility for the data transfer over the network
· Building sites (dredgers destroy cables, etc.)
· Redundancy of the network
· UPS (uninterruptible power supply) for the network components?
To integrate FS NK8000 and management station products into a customer's network,
ensure that your customer is aware of the following information:
· DHCP is not supported from any device;
· NK823x support 10BaseT and 100BaseT, half-duplex and full-duplex mode;
· Only Ethernet RJ 45 copper cable Cat. 5, 5E, or 6 is supported;
· If the network is down, it is not possible to receive any information via the network;
· The responsible person for the network is the customer, and not Siemens
FS/FIS/SES. The customer should sign a contract that Siemens FS/SES disclaims
any liability for the customer's existing network.
Your customer will also need to know the following:
· The IP-address for each NK82xx and each DMS PC (tell where the devices are in-
stalled);
· Redundancy network devices or paths available.
Most companies use a Firewall or a Proxy server to protect the company network from
outside. Also within a company's network, rules exist, and not everything is allowed.
For example, maybe only e-mail and File transfer applications are allowed, and Re-
mote access (Telnet) is prohibited.
Each of these applications has a Port number. This Port number identifies the type of
application. For example the Port number for the e-mail application (SMTP) is 25.
Generally, the network administrator allows only a few Port numbers, and the rest are
prohibited.
049_DMS_DMS8000_Application_Specification_Planning_MP4.81_A6V10063710_a_en.doc
09.2016

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nk8000Mm8000Mk8000

Table of Contents