3.2.11 NK82xx serial configuration

Building Technologies
CPS Fire Safety
Fig. 31
NK8000 serial configuration for MM8000/MK8000 example
Note: Not all subsystems are configurable for MK8000. Refer to section 3.1.
System architecture
This configuration allows for integration of a number of Cerloop (proprietary Class A
loop), Cerban and/or RS485 connectable control panels. In addition it allows for CS6
Guarto integration via LON-bus. One of the NK82xx Serial Ports provides the liaison
for a local management station (MM8000/MK8000).
Communication/connection
The NK82xx is connected on upstream side via RS-232 (proprietary CMSDL protocol)
to the management system.
Note: A (temporary) Ethernet network link is required for configuration download.
On the downstream side, the NK82xx is connected via serial lines and/or via LON-bus
to a number of different fire & security control units.
® For supported downstream configurations/protocols of NK82xx, please refer to the
NK82xx-Ethernet Port Datasheets.
To learn how to obtain these documents, see the Documentation resource informa-
tion section on page 5.
049_DMS_DMS8000_Application_Specification_Planning_MP4.81_A6V10063710_a_en.doc
Automation level configurations
47