IMPORTANT – All audible and visual signaling appliances must be
installed in accordance with all applicable national and local fire alarm
codes and any other required regulatory agencies.
Series Multi-Candela Audible Strobe Appliance (AS -MC) is the
industry's first 2-wire horn strobe alarm appliance that provides 4
selectable candela settings (15, 30, 75, 110). Siemens Audible Strobe
Appliances provide a selectable continuous or code 3 horn tone and
non-synchronized strobe when connected directly to a Fire Alarm
Control Panel (FACP). They can also provide a synchronized code 3
(or March time) horn tone and synchronized strobe when connected to
a notification appliance circuit running the Siemens sync protocol. The
AS-MC Appliance is UL Listed under Standard 1971 for Emergency
Appliances for the Hearing Impaired and UL Standard 464 for Audible
Signal Appliances. The AS-MC is also ULC Listed under Standard
CAN/ULC-S526-02 for Visual Signaling Appliances and Standard
CAN/ULC-S525-99 for Audible Signaling Appliances. This appliance
is listed for wall mounting and indoor use only and is equipped with
a universal mounting plate (UMP) that can be mounted to single-gang,
double-gang, 4" backbox, 100mm European backbox or SHBBS
surface backbox (See wiring and mounting information). The AS-MC
Appliance uses a xenon flashtube with solid state circuitry enclosed in

SPECIFICATIONS:

Operating Voltage (Special Application)
Model*
AS-MC
Description
Continuous Horn
Code 3 Horn
(or March Time)**
NOTES:
1. Strobe will produce 1 flash per second over the Input Voltage range.
2. This strobe/horn model meets the required light distribution patterns defined in UL 1971 and ULC-S526-02.
3. This model is UL/ULC Listed for indoor use with a temperature range of +32  F to +120  F (0  C to +49  C) and maximum humidity of 93%, 2% RH.
The effect of shipping and storage temperatures shall not adversely affect the performance of the appliance when it is stored in the original cartons
and not subjected to misuse or abuse.
When calculating the total current: Use Table 3 to determine the highest value of "RMS Current" for an individual AS Appliance then multiply the value
by the total number of AS Appliances. Be sure to add the currents for any other appliances powered by the same source and include any required
safety factors.
THESE APPLIANCES WERE TESTED TO THE VOLTAGE LIMITS OF 16.0-33.0 VOLTS FOR 24V MODELS USING FILTERED DC OR
UNFILTERED FULL-WAVE -RECTIFIED VOLTAGE. DO NOT APPLY VOLTAGE OUTSIDE OF THIS RANGE.
Note: Refer to the installation instructions for the appropriate NAC to find the maximum allowed voltage drop. Use this value along with the current
draw for the appliance to determine the allowable wire resistance. The maximum wire resistance between strobes shall not exceed 35 ohms.
This appliance is not designed to be used on coded systems in which the applied voltage is cycled on and off.
Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932
P83947-007 C
INSTALLATION INSTRUCTIONS
MULTI-CANDELA AUDIBLE STROBE APPLIANCE
Per UL 1971/464
(VDC/VRMS)
16.0-33.0
Table 2: dBA Sound Output
Volume
Reverberant Per UL 464
16.0VDC
24.0VDC
Low
80
Medium
85
High
88
Low
75
Medium
80
High
84
**Available in sync mode only.
Table 2A: ULC Directional Characteristics
-3 dBA: 48 degrees left, 41 degrees right
-6 dBA: 50 degrees left, 58 degrees right
(WALL MOUNT VERSION)
a polycarbonate lens to provide maximum visibility and reliability for
effective visible signaling.
The AS-MC Appliance can be field set to provide either high (HI) dBA,
medium (MED) dBA or low (LO) dBA sound output.
NOTE: The Code 3 temporal pattern (1/2 second on, 1/2 second off,
1/2 second on, 1/2 second off, 1/2 second on, 1-1/2 off and repeat) is
specified by ANSI and NFPA 72 for standard emergency evacuation
signaling.
evacuation signaling and not for any other purpose.
This model is designed for use with either filtered DC (VDC) or
unfiltered full-wave-rectified (VRMS) input voltage.
polarized for compatibility with standard reverse polarity supervision of
circuit wiring by an FACP.
NOTE: All Canadian installations should be in accordance with the
Canadian Standard for the Installation of Fire Alarm Systems -
CAN/ULC-S524-01 and Canadian Electrical Code, Part 1.
acceptance is subject to authority having jurisdiction (AHJ).
NOTE:
Refer to P/N 315-096363 for the maximum number of
appliances on a single notification appliance circuit.
Table 1: UL/ULC Ratings
Voltage Range Per
CAN/ULC-S526-02/S525-99
(VDC/VRMS)
20.0-31.0
*Available in red and white.
33.0VDC
83
86
88
91
91
93
79
82
84
86
87
90
The Code 3 Horn should be used only for fire
Strobe
Candela
(cd)
15/30/75/110
Anechoic dBA Per CAN/ULC-S525-99 at 10 Feet
20.0VDC
24.0VDC
88
90
93
95
97
99
88
90
93
95
97
99
Siemens Building Technologies, Ltd.
Mississauga Ontario L5N 7A6
All inputs are
Final
Mounting
Options
A,B,C,D
31.0VDC
91
97
100
91
97
100
2185 Derry Road West
Canada

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ah-wAh seriesAs-mc-cwAs-mc-rAh-r

Table of Contents