Commissioning instructions

Sound and Resound alarms options

Resound [FIRE] -> ON / OFF setting
The FIRE ON/OFF setting under [Resound] controls the way sounders operate when a 2nd or subsequent fire occurs after the alarms have been silenced following 1st fire.
SilenceAlarms
Cause and Effect
sounders of 1st Fire
1st Fire
Resound [SOUND] -> ON / OFF setting
The SOUND ON/OFF setting located under [Resound] controls the way sounders operate on 1st press of the Sound Alarms button during a fire condition after the alarms have been silenced. When set
to ON the sounders will resound and when set to OFF the sounders will perform the standard action of all-out alarms.
SilenceAlarms
Cause and Effect
sounders of 1st Fire
1st Fire
See also resound delay mode functions.
148
Resound
SETUP
[FIRE] ->OFF
[FIRE] -> ON
2nd Fire /
subsequent fire
Resound
SETUP
[SOUND] ->OFF
Sound Alarms
[SOUND] -> ON
FACTORY DEFAULT SETTING
Cause and Effect
of 2nd Fire / subsequent fire
Resound
Restores Cause and Effect
of 1st Fire
then
Cause and Effect
of 2nd fire / subsequent fire
FACTORY DEFAULT SETTING
All out
Resound
Restores Cause and Effect
sounders of 1st Fire
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.