Emerson Rosemount 5081 Quick Start Manual page 6

Explosion-proof, single-input intelligent explosion-proof, single-input intelligent transmitter
Hide thumbs Also See for Rosemount 5081:

Advertisement

Quick Start Guide
6. If the transmitter is installed some distance from the sensor, a
remote junction box with preamplifier in the junction box or in the
sensor may be necessary. Consult the sensor reference manual for
maximum cable lengths.
1.2.2
Orient the display board
The display board can be rotated 90 degrees, clockwise or counterclockwise,
from the original position. To reposition the display:
Procedure
1. Loosen the cover lock nut until the tab disengages from the circuit
end cap. Unscrew the cap.
2. Remove the three bolts holding the circuit board stack.
3. Lift and rotate the display board 90 degrees, clockwise or
counterclockwise, into the desired position.
4. Position the display board on the stand offs. Replace and tighten the
bolts.
5. Replace the circuit end cap.
1.3
Hazardous area certifications
1.3.1
IECEx
Certificate
Intrinsically safe marking
Certification conditions
Certification standards
1.3.2
ATEX
Certificate
Intrinsically safe marking
6
IECEx BAS 9.0159X
Ex ia IIC T4 Ga (-20 °C ≤ T
The Rosemount
5081 enclosure may be made of
aluminum alloy and given a protective polyurethane
paint finish; however, care should be taken to prevent it
from impact or abrasion if located in a Zone 0
environment.
IEC 60079-0:2011, IEC 60079-11:2011
Bas02ATEX1284X
Baseef03ATEX0099X
Baseefa03ATEX0399X
Ex ia IIC T4 Ga (-20 °C ≤ T
≤ +65 °C)
amb
(Rosemount
5081A/P)
(Rosemount 5081C)
(Rosemount 5081T)
≤ +65 °C)
amb
Emerson.com/Rosemount
April 2019