Electrical Data

Table 3.
Air temperature rise (60 hz)
2000 CFM (2)
(See Note 2)
No. of
TH/SC072E3
Nominal
Capacity
TH/SC072E4
kW Input
Stages
TH/SC072EW
9.0
1
14.2
11.3
1
14.9
16.9
2
22.3
18.0
1
28.5
22.6
2
29.8
27.0
2
42.7
33.80
2
36.00
2
56.9
54.00
2
1. The air temperature rise (F) across the heaters is: (Heater kW x 3414)/(1.08 x CFM)
2. The minimum allowable airflow for TSC072E with a 36.0 kW heater is 2200 CFM
3. The minimum allowable airflow for WSC072E with a 36.0 kW heater is 2450 CFM
4. The minimum allowable airflow for a TSC120E***B and THC120E with a 54kW heater is 3400 CFM.
5. The minimum allowable airflow for a WSC120 with a 54kW heater is 4000 CFM.
Table 4.
Unit wiring with electric heat (single point connection) - standard efficiency
Unit Model
Heater Model
Tons
Number
Number
6
TSC072E3
BAYHTRS309*
6
TSC072E3
BAYHTRS318*
6
TSC072E3
BAYHTRS327*
6
TSC072E3
BAYHTRS336*
TSC090E3
BAYHTRW309*
TSC090E3
BAYHTRW318*
TSC090E3
BAYHTRW327*
TSC090E3
BAYHTRW336*
(2)
TSC092E3
BAYHTRT309*
(2)
TSC092E3
BAYHTRT318*
(2)
TSC092E3
BAYHTRT327*
(2)
TSC092E3
BAYHTRT336*
8.5
TSC102E3
BAYHTRT309*
8.5
TSC102E3
BAYHTRT318*
8.5
TSC102E3
BAYHTRT327*
8.5
TSC102E3
BAYHTRT336*
10
TSC120E3
BAYHTRA318*
10
TSC120E3
BAYHTRA327*
10
TSC120E3
BAYHTRA336*
10
TSC120E3
BAYHTRA354*
14
6 Ton
7 1/2 Ton
3000 CFM
(See Note 3)
WSC072E3
TSC090E3
WSC072E4
TSC090E4
WSC072EW
TSC090EW
14.2
9.5
14.9
11.9
22.3
17.8
28.5
19.0
29.8
23.8
42.7
28.5
56.9
37.9
Heater kW
Control
(1)
Rating
Stages
208-230 Volts three phase voltage
6.8/9.0
1
13.5/18.0
1
20.3/27.0
2
27.0/36.0
2
6.8/9.0
1
13.5/18.0
1
20.3/27.0
2
27.0/36.0
2
6.8/9.0
1
13.5/18.0
1
20.3/27.0
2
27.0/36.0
2
6.8/9.0
1
13.5/18.0
1
20.3/27.0
2
27.0/36.0
2
13.5/18.0
1
20.3/27.0
2
27.0/36.0
2
40.6/54.0
2
7 1/2 Ton
3000 CFM
WSC090E3
TH/SC092E3
WSC090E4
TH/SC092E4
WSC090EW
TH/SC092EW
9.5
9.5
11.9
17.8
15.7
19.0
19.0
23.8
28.5
28.5
37.9
37.9
Standard Indoor Motor
Max Fuse Size or
Max Circuit
MCA
Breaker
36.5/36.5
50/50
53.1/60.4
60/70
76.6/87.5
80/90
100.1/114.5
110/125
38.2/38.2
60/60
51.4/58.6
60/60
74.9/85.8
80/90
98.4/112.8
100/125
43.3/43.3
50/50
54.8/62.0
60/70
78.3/89.1
80/90
101.8/116.1
110/125
46.3/46.3
60/60
54.8/62.0
60/70
78.3/89.1
80/90
101.8/116.1
110/125
57.5/64.8
60/70
81.0/91.9
90/100
104.5/118.9
110/125
151.4/140.5
175/150
8 1/2 Ton
10 Ton
3400 CFM
4000 CFM
(See note 4) (See note 5)
TH/SC102E3
TH/SC120E3
TH/SC102E4
TH/SC120E4
TH/SC102EW
TH/SC120EW
8.4
15.7
13.4
16.7
14.2
21.0
7.9
25.1
21.3
26.7
33.5
28.5
42.7
Oversized Indoor Motor
MCA
37.8/37.8
54.8/62.0
78.3/89.1
101.8/116.1
44.0/44.0
58.6/65.9
82.1/93.0
105.6/120.0
46.4/46.4
58.6/65.9
82.1/93.0
105.6/120.0
49.4/49.4
58.6/65.9
82.1/93.0
105.6/120.0
—/—
—/—
—/—
—/—
WSC120E3
WSC120E4
WSC120EW
13.4
14.2
17.9
21.3
26.7
28.5
42.7
Max Fuse Size or
Max Circuit
Breaker
60/60
60/70
80/90
110/125
60/60
60/70
90/100
110/125
60/60
60/70
90/100
110/125
60/60
60/70
90/100
110/125
—/—
—/—
—/—
—/—