Inputs / outputs

Analog inputs

Analog input applications

Analog input voltage and current mode

Analog input behavior

7EN05-0390-00
Related Topics
Configuring option module analog inputs using ION Setup
Configuring option module analog outputs using ION Setup
Configuring option module digital inputs using ION Setup
Configuring option module digital outputs using ION Setup
You can use an analog input to monitor an analog signal, for example a flowmeter,
to monitor how much water flows through a pipe.
For analog input operation, your meter takes an analog input signal and provides
the resulting scaled value.
Your meter's analog I/O option modules can measure either low voltage or current
using standard analog transducers such as 4 - 20 mA current transducers.
Related Topics
Option modules
You can set the analog input's mode for voltage or current sensing.
In current mode, the analog inputs have a low input resistance while the meter is
powered on, and a high input resistance when the meter is powered off. In voltage
mode, the analog inputs have a high input resistance regardless of whether the
meter is powered or not.
NOTE: When unpowered, your meter's analog inputs act like they are in
voltage mode (high input resistance).
When connected to a current output transducer, this high resistance can create a
high voltage. Standard (i.e., 4 to 20 mA) current transducers have open circuit
protection and are able to handle a high input resistance; however, if non-standard
transducers are used high voltages may be generated. Your meter's analog input
has circuitry to limit this voltage, but it may not be sufficient with a very high-power
current source.
EQUIPMENT DAMAGE
Failure to follow these instructions will result in equipment damage.
Ensure the analog input is configured for the correct voltage or current mode
before connecting or activating the current transducer.
Do not exceed the device's ratings for maximum limits.
Related Topics
Option modules
Analog inputs may show a value below zero scale if an open circuit is detected on
the input port.