3-10
tart up
Refrigeration
Controls
Model
Product
Application
HGM
Medium Temp
Self Contained
and remote
CONTROLS AND ADJUSTMENTS
See table above for merchandiser operation.
REFRIGERANT CONTROL
Refrigerant flow to the evaporator is con-
trolled through the use of a capillary tube.
Because the suction line capillary tube assem-
bly, sometimes referred to as heat exchanger or
pull-out coil has no moving parts, it will rarely
need servicing. However, if a leak occurs in
the refrigeration system, it is possibly that dirt,
dust, or moisture may collect in the capillary
tube causing the system to go into a vacuum.
Should this occur, it is recommended that dry
nitrogen or a dry refrigerant be forced through
the system to clear blockage.
P/N 0515297_E
/ O
peratiOn
CONTROLS and ADJUSTMENTS
Discharge Air
Temperature
28 F to 36 F
U.S. & Canada 1-800-922-1919 • Mexico 1-800-890-2900 • www.hussmann.com
Defrost Controls
Defrost
Type of
Frequency
Defrost
(per day)
OFF
2
CYCLE
If an attempt to clear the restriction by this
method are unsuccessful, the entire assembly,
not the capillary tube only, should be replaced
with a new factory ordered replacement.
Termination
Failsafe
Temperature
Time
(Minutes)
48 F
30