Installation Clearances; Line Set; Electrical Connections - Lennox Elite ELS Series Installation Instructions Manual

6 – 20 ton
Table of Contents

Advertisement

Installation Clearances

See Unit Dimensions on page 2 for sizing mounting slab,
platforms or supports. Refer to figures 4 through 6 for
mandatory installation clearance requirements.
NOTES:
• Clearance to one of the remaining two sides may be 12
in. (305 mm) and the final side may be 6 in. (152 mm).
• A clearance of 24 in. (610 mm) must be maintained be-
tween two units.
• 48 in. (1219 mm) clearance required on top of unit.
SEE
NOTES
FIGURE 4. ELS072 and ELS090
Installation Clearances
SEE
NOTES
FIGURE 5. ELS120S4S, ELS120S4D
and ELS150 Installation Clearances
30"
CONTROL BOX
(762)
ACCESS
36"
(914)
SEE
NOTES
SEE
NOTES
30"
CONTROL BOX
ACCESS
36"
SEE
NOTES
FIGURE 6. ELS180 and ELS240
Installation Clearances

Line Set

Field refrigerant piping consists of liquid and suction lines
connecting the condensing unit and the indoor unit. Liquid
and suction service valves are located in a compartment
at the corner of the unit below the control box.
Piping can be routed directly from the service valves or
field supplied elbows can be added to divert the piping as
required.
Refer to table 1 for field-fabricated refrigerant line sizes for
runs up to 50 linear feet (15 m).
TABLE 1. Refrigerant Line Sizes for Runs
Unit
ELS072
ELS090
ELS120S4S
ELS120S4D
ELS150
ELS180
ELS240
Refrigerant Line Limitations
You may install the unit in applications that have line set
lengths of up to 50 linear feet (15 m) with refrigerant line
sizes as outlined in table 1 (excluding equivalent length of
fittings). Size refrigerant lines greater than 50 linear feet
(15m or greater) according to the Lennox Refrigerant Pip-
ing Design and Fabrication Guidelines (Corp. 9351-L9) or
latest version.

Electrical Connections

In the United States, wiring must conform with current lo-
cal codes and the current National Electric Code (NEC). In
Canada, wiring must conform with current local codes and
the current Canadian Electrical Code (CEC).
Page 13
30"
BOX ACCESS
SEE
NOTES
Up to 50 Linear Feet
Liquid Line
Suction Line
3/8" (10mm)
1-1/8" (29mm)
5/8" (16mm)
1-1/8" (29mm)
5/8" (16mm)
1-1/8" (29mm)
3/8" (10mm)
1-1/8" (29mm)
3/8" (10mm)
1-1/8" (29mm)
5/8" (16mm)
1-1/8" (29mm)
5/8" (16mm)
1-1/8" (29mm)
CONTROL
36"