A.12 Settings

NOTE: The following table lists all data which are available in the maximum complement of the device. De-
pendent on the ordered model, only those data may be present which are valid for the individual version.
Addr.
Setting Title
201
STRPNT->OBJ S1
202
IN-PRI I-SIDE1
203
IN-SEC I-SIDE1
204
CT ANGLE W0
205
FACTOR IEE1
210
STRPNT->OBJ S2
211
IN-PRI I-SIDE2
212
IN-SEC I-SIDE2
213
FACTOR IEE2
214
GRD TERM. IEE2
221
Unom PRIMARY
222
Unom SECON-
DARY
223
UE CONNECTION
224
FACTOR UE
225A
Uph / Udelta
241
UN-PRI SIDE 1
7UM62 Manual
C53000-G1176-C149-3
Function
Setting Options
Power System
YES
Data 1
NO
Power System
1..100000 A
Data 1
Power System
1A
Data 1
5A
-5.00..5.00 °
Power System
Data 1
Power System
1.0..100000.0
Data 1
Power System
YES
Data 1
NO
Power System
1..100000 A
Data 1
Power System
1A
Data 1
5A
Power System
1.0..100000.0
Data 1
Power System
Terminal Q7
Data 1
Terminal Q8
Power System
0.10..400.00 kV
Data 1
Power System
100..125 V
Data 1
Power System
UE connected to
Data 1
neutral transformer
UE connected to
broken delta win-
ding
not connected
UE connected to
any VT
UE connected to
Rotor
UE connected to
Loading Resistor
Power System
1.0..2500.0
Data 1
Power System
1.00..3.00
Data 1
Power System
0.40..800.00 kV
Data 1
Default Setting
YES
CT-Strpnt. Side1 in Direct.
of Object
500 A
CT Rated Primary Current
Side 1
1A
CT Rated Secondary Cur-
rent Side 1
0.00 °
Correction Angle CT W0
60.0
CT Ratio Prim./Sec. IEE1
YES
CT-Strpnt. Side2 in Direct.
of Object
500 A
CT Rated Primary Current
Side 2
1A
CT Rated Secondary Cur-
rent Side 2
60.0
CT Ratio Prim./Sec. IEE2
Terminal Q7
Grounded Terminal CT
IEE2
6.30 kV
Rated Primary Voltage
100 V
Rated Secondary Voltage
(Ph-Ph)
UE connected to
UE Connection
neutral transformer
36.4
VT Ratio Prim./Sec. Ue
1.73
Matching Ratio Ph.-VT to
Broken-Delta-VT
20.00 kV
Rated Primary Voltage Side
1
A.12 Settings