Maintenance
9.5 Repair
9. Fasten the four eyebolts
10.Lift up the phase module and put it to one side.
11.Now lift the new phase module in the same manner from the transport packaging. Place the
See also
Attaching the changing device to the stacker (Page 152)
Installing a phase module
Installing the module
1. Install the intact module in the reverse order of the previously described steps.
2. When tightening the screws, make sure that you use the appropriate torque (Page 147)
3. Tighten the joints between the water pipes by hand.
Performing final checks
1. Open the valves.
2. Make sure that the connections are tight.
3. Make sure that the flow is ensured once the re-cooling unit has been switched in.
160
the eyelets on the fork.
phase module on the changing device.
permissible for each screw type.
on the phase module. Position the stacker so that you can hang
SINAMICS SM150 6SL3845-2NN41-8AD0
Operating Instructions Rev.201908010908 EXAMPLE