7.6.3 Configuring a Channel

An I/O Module will be set into Configuration State if configuration update is attempted for any of its channels
Note: You will need to have the required configuration information available before starting this procedure or
you risk the system timing you out and decommissioning the uncompleted channel and losing all your
Configuration State means that all commissioned channels on the I/O Module are set into Inhibit state – i.e. the
unsaved changes.
input channels will not trigger any alarms and output channels will not execute any actions.
You should consider alternative safety measures when performing these procedures.
To configure an individual channel:
1) Login as an Service or higher access level
2) Select Menu > Configuration > Channel settings.
3) Select the required Module type.
4) Select a required channel and touch 'Select'.
5) Select Enable for a required channel
6) Select Channel Number and Enter Channel Tag
7) Select a detector name and a sensor type to import all relevant configuration parameters from the Sensor
Catalog.
8) Edit the channel parameters
9) Touch Finish if modification of channel settings is complete
10) Check whether the channel settings are valid before making it take effect
11) Touch Apply
Commissioning
CAUTION – ALARM INHIBIT
(i.e. Commission Channel or Edit Configuration).
62