5.2
Suspension Bolts and Piping Connections
(1) Mark the positions of the suspension bolts, refrigerant pipe connections and condensate pipe
connection.
(2) Installation dimensions are shown in Figure 5.2.
2-9/16 x 1-3/8 [65 x 35]
(for Suspension Bolt)
Refrigerant Gas Pipe Connection
Refrigerant Liquid Pipe Connection
Condensate Pipe Connection
5.3
Mounting Indoor Unit
Hang the indoor unit as shown in Figure 5.3.
Field-Supplied Parts
* Suspension Bolts: 4-M10 or W3/8
* Nut: 8-M10 or W3/8
10
52-3/8 [1330] (for Suspension Bolt)
49-3/16 [1250]
39-3/8 [1000]
56 - φ1/8 [3]
Around the Flange
60 - φ1/8 [3]
Around the Flange
41-5/16 [1050]
Figure 5.2 Suspension Bolts
Suspension Bolts (4-M10 or W3/8)
(Field-Supplied)
Suspension
Bracket
1-15/16 [50]
1-15/16 [50]
4-7/16
[113]
Unit
False Ceiling Side
Vibration-proof
Rubber
(Accessory)
Figure 5.3 Mounting Indoor Unit
Unit: inch [mm]
1-9/16 [40]
5-7/16
[138]
Nut & Washer
(8-M10 or W3/8)
P01432Q-rev.1