Carrier WeatherMaster 50HC04 Service And Maintenance Instructions page 52

Single package rooftop electric cooling unit with puron (r-410a) refrigerant
Hide thumbs Also See for WeatherMaster 50HC04:
Table of Contents

Advertisement

Table 22 — Dry Bulb Operation with DCV (CO
DEMAND
OUTSIDE AIR
CONTROLLED
GOOD TO
VENTILATION (DCV)
ECONOMIZE
Below CO
Set
2
Above CO
Set
2
*With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for sec-
ond stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
†With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and
Y2-I have not been satisfied.
Table 23 — Enthalpy Operation without DCV (CO
DEMAND
OUTSIDE AIR
CONTROLLED
GOOD TO
VENTILATION (DCV)
ECONOMIZE
NO CO
SENSOR
2
*With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second
stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
†With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and
Y2-I have not been satisfied.
Y1-I
Y2-I
OFF
OFF
No
ON
OFF
ON
ON
OFF
OFF
ON
OFF
Yes
ON
ON
OFF
OFF
No
ON
OFF
ON
ON
OFF
OFF
Yes
ON
OFF
ON
ON
Y1-I
Y2-I
OFF
OFF
NO
ON
OFF
ON
ON
OFF
OFF
ON
OFF
YES
ON
ON
Sensor) — 2 Speed Fan
2
FAN
Y1-O
Y2-O
SPEED
LOW
0v/Off
0v/Off
LOW
24v/On
0v/Off
HIGH
24v/On
24v/On
LOW
0v/Off
0v/Off
LOW
0v/Off
0v/Off
HIGH
24v/On
0v/Off
LOW
0v/Off
0v/Off
LOW
24v/On
0v/Off
HIGH
24v/On
24v/On
LOW
0v/Off
0v/Off
LOW
0v/Off
0v/Off
DELAY*
HIGH
0v/Off†
24v/On
Sensor) — 2 Speed Fan
2
FAN
Y1-O
Y2-O
SPEED
LOW
0v/Off
0v/Off
LOW
24v/On
0v/Off
HIGH
24v/On
24v/On
LOW
0v/Off
0v/Off
LOW
0v/Off
0v/Off
DELAY*
HIGH
0v/Off†
24v/On
52
OCCUPIED
UNOCCUPIED
VENTMIN
VENTMIN
VENTMIN
VENTMIN
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
Closed to Full-Open
Full-Open
OCCUPIED
UNOCCUPIED
MIN POS
MIN POS
MIN POS
MIN POS
MIN POS to Full Open
Closed to Full-Open
MIN POS to Full Open
Closed to Full-Open
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed