Economi$Er Iv Preparation; Differential Enthalpy; Single Enthalpy; Dcv (Demand Controlled Ventilation) And Power - Carrier WeatherMaster 50HC04 Service And Maintenance Instructions

Single package rooftop electric cooling unit with puron (r-410a) refrigerant
Hide thumbs Also See for WeatherMaster 50HC04:
Table of Contents

Advertisement

DEHUMIDIFICATION OF FRESH AIR WITH DCV
(DEMAND CONTROLLED VENTILATION) CONTROL
If normal rooftop heating and cooling operation is not adequate
for the outdoor humidity level, an energy recovery unit and/or
a dehumidification option should be considered.

EconoMi$er IV Preparation

This procedure is used to prepare the EconoMi$er IV for trou-
bleshooting. No troubleshooting or testing is done by perform-
ing the following procedure.
NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm resis-
tor, and a 5.6 kilo-ohm resistor which are not supplied with the
EconoMi$er IV.
IMPORTANT: Be sure to record the positions of all
potentiometers before starting troubleshooting.
1.
Disconnect power at TR and TR1. All LEDs should be off.
Exhaust fan contacts should be open.
2.
Disconnect device at P and P1.
3.
Jumper P to P1.
4.
Disconnect wires at T and T1. Place 5.6 kilo-ohm resistor
across T and T1.
5.
Jumper TR to 1.
6.
Jumper TR to N.
7.
If connected, remove sensor from terminals SO and +.
Connect 1.2 kilo-ohm 4074EJM checkout resistor across
terminals SO and +.
8.
Put 620-ohm resistor across terminals SR and +.
9.
Set minimum position, DCV set point, and exhaust poten-
tiometers fully CCW (counterclockwise).
10. Set DCV maximum position potentiometer fully CW
(clockwise).
11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.

Differential Enthalpy

To check differential enthalpy:
1.
Make sure EconoMi$er IV preparation procedure has been
performed.
2.
Place 620-ohm resistor across SO and +.
3.
Place 1.2 kilo-ohm resistor across SR and +. The Free
Cool LED should be lit.
4.
Remove 620-ohm resistor across SO and +. The Free Cool
LED should turn off.
5.
Return EconoMi$er IV settings and wiring to normal after
completing troubleshooting.

Single Enthalpy

To check single enthalpy:
1.
Make sure EconoMi$er IV preparation procedure has been
performed.
2.
Set the enthalpy potentiometer to A (fully CCW). The
Free Cool LED should be lit.
3.
Set the enthalpy potentiometer to D (fully CW). The Free
Cool LED should turn off.
4.
Return EconoMi$er IV settings and wiring to normal after
completing troubleshooting.

DCV (Demand Controlled Ventilation) and Power

Exhaust

To check DCV and Power Exhaust:
1.
Make sure EconoMi$er IV preparation procedure has been
performed.
2.
Ensure terminals AQ and AQ1 are open. The LED for
both DCV and Exhaust should be off. The actuator should
be fully closed.
3.
Connect a 9-v battery to AQ (positive node) and AQ1
(negative node). The LED for both DCV and Exhaust
should turn on. The actuator should drive to between 90
and 95% open.
4.
Turn the Exhaust potentiometer CW until the Exhaust
LED turns off. The LED should turn off when the potenti-
ometer is approximately 90%. The actuator should remain
in position.
5.
Turn the DCV set point potentiometer CW until the DCV
LED turns off. The DCV LED should turn off when the
potentiometer is approximately 9-v. The actuator should
drive fully closed.
6.
Turn the DCV and Exhaust potentiometers CCW until the
Exhaust LED turns on. The exhaust contacts will close 30
to 120 seconds after the Exhaust LED turns on.
7.
Return EconoMi$er IV settings and wiring to normal after
completing troubleshooting.

DCV Minimum and Maximum Position

To check the DCV minimum and maximum position:
1.
Make sure EconoMi$er IV preparation procedure has been
performed.
2.
Connect a 9-v battery to AQ (positive node) and AQ1
(negative node). The DCV LED should turn on. The actua-
tor should drive to between 90 and 95% open.
3.
Turn the DCV Maximum Position potentiometer to mid-
point. The actuator should drive to between 20 and 80%
open.
4.
Turn the DCV Maximum Position potentiometer to fully
CCW. The actuator should drive fully closed.
5.
Turn the Minimum Position potentiometer to mid-point.
The actuator should drive to between 20 and 80% open.
6.
Turn the Minimum Position Potentiometer fully CW. The
actuator should drive fully open.
7.
Remove the jumper from TR and N. The actuator should
drive fully closed.
8.
Return EconoMi$er IV settings and wiring to normal after
completing troubleshooting.

Supply-Air Sensor Input

To check supply-air sensor input:
1.
Make sure EconoMi$er IV preparation procedure has been
performed.
2.
Set the Enthalpy potentiometer to A. The Free Cool LED
turns on. The actuator should drive to between 20 and 80%
open.
3.
Remove the 5.6 kilo-ohm resistor and jumper T to T1. The
actuator should drive fully open.
4.
Remove the jumper across T and T1. The actuator should
drive fully closed.
5.
Return EconoMi$er IV settings and wiring to normal after
completing troubleshooting.

EconoMi$er IV Troubleshooting Completion

This procedure is used to return the EconoMi$er IV to opera-
tion. No troubleshooting or testing is done by performing the
following procedure.
1.
Disconnect power at TR and TR1.
2.
Set enthalpy potentiometer to previous setting.
3.
Set DCV maximum position potentiometer to previous
setting.
40