Flue Terminal Positions - Bosch Worcester GREENSTAR CDi Series Instruction Manual

Wall hung rsf gas-fired condensing combination boiler for sealed central heating systems and mains fed domestic hot water
Table of Contents

Advertisement

Minimum dimensions of flue terminal positions for balanced room sealed flues with
fanned draught:
DRWG.
TERMINAL POSITION
DISTANCE
REF:
A'
Directly below an opening, air brick, opening windows, etc.
300mm
B '
Above an opening, air brick, opening window, etc.
300mm
C'
Horizontally to an opening, air brick, opening window, etc.
300mm
D
Below gutters, soil pipes or drain pipes
75mm
E
Below eaves
200mm
F2
Below balconies or car port roof (lowest point)
200mm
G
From a vertical drain pipe or soil pipe
150mm
H
From an internal or external corner
300mm
I
Above ground, roof or balcony
300mm
J
From a surface facing the terminal
600mm
K
From a terminal facing the terminal
1200mm
L2
From an opening in the car port (e.g. door, window) into the dwelling
1200mm
M
Vertically from a terminal on the same wall
1500mm
N
Horizontally from a terminal on the same wall
300mm
0
From a non combustible vertical structure on the roof
*
p
Above intersection with roof
*
0
Adjacent to windows or openings on pitched and flat roofs
600mm
R
Below windows or openings on pitched roofs
2000mm
In addition, the terminal should not be nearer than 150mm (fanned draught} to an opening
in the building fabric formed for the purpose of accommodating a built-in element such as a
window frame.
2 Not recommended.
*
See instructions supplied with vertical flue kits.
FLUE TERMINAL POSITIONS
The flue must be fitted and terminated in
accordance with the recommendations of
BS5440 : Part
1.
The flue must not cause an obstruction.
Discharge and any noise from the flue outlet
must not cause a nuisance.
Flue gases have a tendency to plume and in
certain weather conditions a white plume of
condensation will be discharged from the
flue outlet. Where this could be a nuisance,
for example, near security lighting, an alter-
nate position should be found.
The air inlet/outlet duct and the terminal of
the boiler must not be closer than 25mm to
any combustible material.
Detailed recommendations on protection of
combustible materials are given in
BS 5440:1
A protective terminal guard must be fitted if
the terminal is 2m or less above a surface to
which people have access.
The guard must be spaced equally (mini-
mum 50 mm) around the flue and fixed to
the wall with plated screws. See Contact
Information (inside front cover).
FLUE TERMINAL POSITIONS
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER BOSCH GREENSTAR 25CDI/30CDI/37CDI/42