Power Supply; Rin-Apu24 - Honeywell CENTRA LINE EAGLEHAWK NX Installation & Commissioning Instructions

Table of Contents

Advertisement

EAGLEHAWK NX CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

Power Supply

Powering EAGLEHAWK NX
Power is supplied via a removable terminal plug (attached to
terminals 1 and 2).
The power supply of the EAGLEHAWK NX controller must
conform to Safety Class II. To reduce overall current con-
sumption, the EAGLEHAWK NX can be powered by a switch
power supply (rather than by a transformer). See also Table 2
on pg. 3.
NOTE: Due to the risk of short-circuiting (see Fig. 23), it is
strongly recommended that the EAGLEHAWK NX
controller be supplied with power from a dedicated
transformer. However, if the EAGLEHAWK NX con-
troller is to be supplied by the same transformer
powering other controllers or devices (e.g., the PW
M-Bus Adapter), care must be taken to ensure that
correct polarity is observed.
N, L
EARTH GROUND
SHORT-CIRCUITING!
CPU 1
USB 2.0
Device Interface
24V~0
24V~
1
2
24
V~
L
LINE
N
24 V~0
NOISE-FREE EARTH GROUND
(ONLY ONE PER SYSTEM)
Fig. 23. Incorrect polarity → SHORT-CIRCUITING!
Transformer Data
In Europe, if the EAGLEHAWK NX is powered by trans-
formers, then such transformers must be safety isolating
transformers conforming to IEC61558-2-6. In the U.S. and
Canada, if the EAGLEHAWK NX is powered by transformers,
then such transformers must be NEC Class-2 transformers.
EN1Z-1039GE51 R1218
PC 1
PC 2
CPU 2
24V~0
24V~
1
2
REVERSED
!
POLARITY!
Table 9. 1450 series transformers data
part #
primary side
1450 7287
-001
120 VAC
-002
120 VAC
-003
120 VAC
-004
240/220 VAC
-005
240/220 VAC
-006
240/220 VAC
Table 10. Overview of CRT Series AC/DC current
transformer
primary side
CRT 2
230 VAC
CRT 6
230 VAC
CRT 12
230 VAC
PRIMARY SIDE
230 VAC
24 VAC
24 V0
120 VAC
NOT
RECOMMENDED
Fig. 24. Connection of EAGLEHAWK NX controller

RIN-APU24

The RIN-APU24 Uninterruptable Power Supply can be
directly wired to an EAGLEHAWK NX controller.
See RIN-APU24 Uninterruptable Power Supply – Mounting
Instructions (EN0B-0382GE51) for a detailed wiring diagram.
Powering Panel Bus I/O Modules and Field Devices
The EAGLEHAWK NX, Panel Bus I/O modules, and field
devices can be powered by either separate transformers (see
Fig. 25, and Fig. 26) or by the same transformer.
NOTE: Use a min. distance of 10 cm between power cables
and 0...10 V / sensor cables in order to prevent
signal disturbances on the 0...10 V / sensor cables.
See also section "Addressing Panel Bus I/O
Modules" on page 35.
22
secondary side
24 VAC, 50 VA
2 x 24 VAC, 40 VA, 100 VA
from separate transformer
24 VAC, 100 VA, 24 VDC,
600 mA
24 VAC, 50 VA
2 x 24 VAC, 40 VA, 100 VA
from separate transformer
24 VAC, 100 VA, 24 VDC,
600 mA
max. AC
max. DC
current
current
2 A
500 mA
6 A
1300 mA
12 A
2500 mA
EAGLEHAWK NX
2
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents