M-Bus Connection Procedure - Honeywell CENTRA LINE EAGLEHAWK NX Installation & Commissioning Instructions

Table of Contents

Advertisement

EAGLEHAWK NX CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

M-Bus Connection Procedure

1.
Install the PW M-Bus Adapter on DIN rail. Insert a
screwdriver into the slot in the DIN rail clamp on the
underside of the PW and pry downward to loosen clamp
until the unit snaps onto the rail.
DIN RAIL
3
1
Fig. 54. Mounting of PW (PW3 shown here)
2.
Connect the M-Bus devices to the PW M-Bus Adapter.
All M+ and M- terminals are connected in parallel in the
PW M-Bus Adapter.
Fig. 55. PW M-Bus adapter connections
3.
Connect the PW M-Bus Adapter to the RS232 / RJ45
socket of the EAGLEHAWK NX using the XW586 cable.
2
INSERT
METER-BUS
WIRES
XW586
INSERT POWER
SUPPLY WIRES
EAGLEHAWK NX
M-BUS
DEVICE
Fig. 56. Connecting the EAGLEHAWK NX to the PW M-
4.
Connect 24 V power to the M-Bus Adapter.
WARNING
Risk of electric shock or equipment damage!
Due to the risk of short-circuiting (see Fig. 23), it is strongly
recommended that the EAGLEHAWK NX controller be
supplied with power from a dedicated transformer.
However, if the EAGLEHAWK NX controller is to be
supplied by the same transformer powering other con-
trollers or devices (e.g., the PW M-Bus Adapter), care
must be taken to ensure that correct polarity is observed.
!
230 VAC
120 VAC
230 VAC
120 VAC
230 VAC
120 VAC
230 VAC
120 VAC
Fig. 57. Connecting power to the PW M-Bus adapter
47
RS232 / RJ45
SOCKET
XW586
Bus adapter
EAGLEHAWK NX
EAGLEHAWK NX
PANTHER,
TIGER, LION,
etc.
PW3, PW20,
PW60, etc.
24 VAC
EAGLEHAWK NX
0 V
24 VAC
EAGLEHAWK NX
0 V
PANTHER,
24 VAC
TIGER, LION,
0 V
etc.
PW3, PW20,
24 VAC
PW60, etc.
0 V
EN1Z-1039GE51 R1218