Blower Performance Data - Heat Controller HEV Series Engineering Design Manual

Residential packaged geothermal heat pump, 2 to 5 tons
Table of Contents

Advertisement

Design Guide
Engineering Design Guide

Blower Performance Data

Air ow in CFM with wet coil and clean air  lter
Fan
Max ESP
Model
Motor
(in. wg)
(hp)
024
0.75
1/2
030
0.5
1/2
036
0.6
1/2
042
0.6
3/4
048
0.75
3/4
060
0.75
Air ow is controlled within 5% up to the Max ESP shown with wet coil
Factory shipped on default CFM
Cooling Mode
Range
Stg 2
Default
750
Maximum
850
Minimum
600
Default
950
Maximum
1100
Minimum
750
Default
1125
Maximum
1250
Minimum
900
Default
1300
Maximum
1475
Minimum
1050
Default
1500
Maximum
1700
Minimum
1200
Default
1875
1
Maximum
2100
Minimum
1500
HEV-HEH SEriES
HEV/H SERIES
Dehumid Mode
Stg 1
Stg 2
Stg 1
575
650
500
650
800
600
450
600
450
650
800
575
750
1000
700
525
750
525
750
975
650
950
1200
800
600
900
600
925
1125
825
1100
1400
1000
750
1050
750
1125
1300
975
1300
1600
1200
900
1200
900
1500
1625
1300
1700
2000
1600
1200
1500
1200
24
Heat Controller
Heating Mode
Fan Only
Mode
Stg 2
Stg 1
750
575
350
850
850
850
600
450
300
950
650
450
1100
1100
1100
750
525
375
1125
750
525
1250
1250
1250
900
600
450
1300
925
600
1475
1475
1475
1050
750
525
1500
1125
700
1700
1700
1700
1200
900
600
1875
1500
875
2100
2100
2100
1500
1200
750
Heat Controller, LLC
Aux/
Emerg
Mode
750
850
650
950
1100
750
1125
1250
900
1300
1475
1050
1500
1700
1350
1875
2100
1500

Hide quick links: