Connection Status Bacnet Bus - Siemens SIMATIC PN/BACnet LINK Operating Instructions Manual

Network transitions
Table of Contents

Advertisement

10.1.2

Connection status BACnet bus

Connection status BACnet bus
The PN/BACnet LINK signals its state with the BACnet LEDs on the front of the housing.
Figure 10-2
Table 10- 1
RUN LED
Flashes
Note
Definition of RUN state
The RUN state is defined as follows: PN/BACnet server is in the OPERATIONAL state and
the client function is enabled for configured client references.
PN/BACnet LINK
Operating Instructions, 10/2017, A5E39895543-AA
Status LEDS BACnet bus
Behavior of the RUN LED
Meaning
The PN/BACnet LINK is
not in RUN operating state
Off
The PN/BACnet LINK is in
RUN state.
On
The PN/BACnet LINK is in
CONFIGURATION state.
Note
Server: System_Status is not OPERATIONAL
or
If client references are configured: Status =
INACTIVE (0)
Server: System_Status is OPERATIONAL
and
If client references are configured: Status =
ACTIVE (1)
Device is waiting for HWConfig from the CPU. The old
configuration (if any) is discarded.
When foreign device registration is activated, the de-
vice waits for the result of the registration.
New Server objects and/or object references are cre-
ated. This may take up to 30 seconds. During this time,
the PN/BACnet LINK is not accessible for the other
BACnet devices.
Diagnostics
10.1 Status LEDs
79