Esd Guidelines; Esd-Sensitive Components - Siemens SINAMICS PERFECT HARMONY GH180 Function Manual

Advanced motor protection for type: 6sr variable frequency drives
Hide thumbs Also See for SINAMICS PERFECT HARMONY GH180:
Table of Contents

Advertisement

ESD guidelines

A.1

ESD-sensitive Components

Guidelines for Handling Electrostatic Sensitive Devices (ESD)
NOTICE
ESD Sensitive Equipment
● Always be aware of electrostatic discharge (ESD) when working near or touching
● Always transport static sensitive equipment in antistatic bags.
● Always use a soldering iron that has a grounded tip. Also, use either a metallic vacuum-
● Ensure that anyone handling the printed circuit boards is wearing a properly grounded
● Static charge build-up can be removed from a conductive object by touching the object with
● When handling a PC board, always hold the card by its edges.
● Do not slide printed circuit boards (PCBs) across any surface (e.g., a table or work bench).
● Avoid plastic Styrofoam™, vinyl and other non-conductive materials. They are excellent
● When returning components to Siemens Industry, Inc. always use static-safe packing. This
Advanced Motor Protection for Variable Speed Operation
Manual, AA, A5E46373908A
components inside the VFD cabinet. The printed circuit boards contain components that
are sensitive to electrostatic discharge. Handling and servicing of components that are
sensitive to ESD should be done only by qualified personnel and only after reading and
understanding proper ESD techniques. The following ESD guidelines should be observed.
Following these rules can greatly reduce the possibility of ESD damage to printed circuit
board (PCB) components.
style plunger or copper braid when desoldering.
static strap. The wrist strap should be connected to ground through a 1 Megohm resistor.
Grounding kits are available commercially through most electronic wholesalers.
a properly grounded piece of metal.
If possible, perform PCB maintenance at a workstation that has a conductive covering that
is grounded through a 1 Megohm resistor. If a conductive tabletop cover is unavailable, a
clean steel or aluminum tabletop is an excellent substitute.
static generators and do not give up their charge easily.
limits any further component damage due to ESD.