SAFETY APPLICATION CONFIGURATION EXAMPLE

5.3.2 Safety remote station parameter settings

Set the safety remote station parameter settings as follows.
Module
Model name
QS0J65BTB2-12DT
Module technical
*1
version
Specify production
information to find
Yes (check)
module
Production
1100000000000010
*2
information
Parameter
Table5.5 Safety remote station parameter settings
(1)
(2)
SR_IO1
SR_IO2
QS0J65BTB2-12DT
A
No (no check)
Indicated in each case example of Section 5.6 or later.
*1: For Module technical version, check the rated plate on the module side in the corresponding safety
remote station.
CC-Link Safety System Remote I/O Module User's Manual QS0J65BTB2-12DT
*2: Enter Production information field referring to the rated plate on the module side in the
corresponding safety remote station.
CC-Link Safety System Remote I/O Module User's Manual QS0J65BTB2-12DT
The use of production information is needed to maintain a proper function after module exchange or
to detect any incorrect station number settings such as station number duplication. Use the
production information to use safety PLC properly and safely.
(3)
SR_IO3
QS0J65BTB2-12DT
A
A
No (no check)
5.3 CC-Link Parameter Settings
5.3.2 Safety remote station parameter settings
(4)
SR_IO4
QS0J65BTB2-12DT
A
Yes (check)
1100000000000020
5
- 5
1
2
3
4
5