12. External input and output
With using external input and output functions, this product can be operated inter-connectedly with
an external device.
Connector
CN10
Low noise mode
CN11
Peak cut mode
CN12
CN13
12-1. External input
With using external input function, on/off status of "Low noise mode" and "Peak cut mode" can be
specified by the external signal.
Low noise mode
In following condition, the operating noise of the outdoor unit reduces comparing from the one in
normal operating condition:
The air conditioner is set to the "Low noise mode" when closing the contact input of a commercial
timer or on/off switch to a connector on the control PCB of the outdoor unit
NOTE: Product performance may drop depending on some conditions such as the outdoor
temperature.
Circuit diagram example
Outdoor unit
control PCB
Connector
1
2
Input signal
Low noise mode
Optional part
Part name
External connect kit
Input
—
—
Compressor status
• Contact capacity: DC 24 V or more, 10 mA or more.
• *: Make the distance from the PCB to the connected unit
Connected unit
within 33 ft (10 m).
Example: Switch
• Construct a circuit as shown in this figure with using
optional parts mentioned below.
• Input signal: On in "Low noise mode"
• Input signal: Off in normal operation
33 ft. (10 m)*
• To set the level of "Low noise mode", refer to
mode"
Signal
Locally purchased
On
Off
On
Off
Model name
UTY-XWZXZ3
- 74 -
Output
—
—
Error status
on page 80.
Remarks
See external input/output
settings for details.
"Low noise
Exterior