Fujitsu Airstage VR-II Series Service Manual page 126

Table of Contents

Advertisement

Trouble shooting 33
OUTDOOR UNIT Error Method:
Rush Current Limiting Resistor
Temp Rise Protection
Detective Actuators:
Inverter PCB
Forecast of Cause :
1. Magnetic relay (for INV) coil side wiring disconnection, open
2. Power supply to Filter PCB (INV) to Inverter PCB wiring disconnection, open
3. Magnetic relay activation circuit defective
4. Main PCB to Inverter PCB wiring disconnection, open
5. Main PCB output
Check Point 1 : Check the magnetic relay (for invertert) coil side wiring
Connector and wiring connection state check
Cable open check
OK
Check Point 2 : Check Power supply to Filter PCB (INV) to inverter PCB wiring
Connector and wiring connection state check
Cable open check
OK
Check Point 3-1 : Magnetic relay activation circuit
Chack the DC Voltage (12V) of
OK
Check Point 4 : Check the wiring (Main PCB to Inverter PCB)
Check the wiring connection.
(CN138 on Main PCB to CN330 on Inverter PCB)
OK
Check Point 5 : Main PCB output
Check the
AC208- 230V
of CN130 on Main PCB
OK
Check Point 6 : Replace Main PCB
Change Main PCB and set up the original address.
After fixing the problem and for canceling the Error, Error Reset (F3-40) will be required after power reset
Caution
By changing of DIP SW 4-2 to ON, the Back-up operation can start when the active outdoor unit exists on the multi outdoor unit connection.
(Stand alone outdoor unit is impossible)
The following conditions will be concerned in use of back-up operation. (Please do not use the system with back-up operation for long time.)
- The operating compressor life time becomes shorter.
- The operating performance may drop due to the limited active compressor(s).
- The compressor may stop frequently by protection controlling.
*In order to keep the operating capacity, the release of the Low noise mode setting might be necessary.
Indicate or Display:
E68. 2
Outdoor Unit : E. 6 8. 2
Indoor Unit
Error Code
Detective details:
"Protection stop by "Rush current limiting resistor temperature rise detection''
of inverter PCB" was generated 2 times.
AC208- 230V
Main PCB defective (output
CN330 on
INVERTER PCB
AC208- 230V
for Magnetic relay
: Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
: 9 U / 6 8
on CN130 defective
on CN130 for Magnetic relay (INV) defective)
AC208- 230V
NG
Replace Inverter PCB
04-42