Download Print this page

Carrier 140/E Series Installation, Start--Up, Operating, And Service And Maintenance page 10

Single-stage deluxe, induced-combustion 4-way multipoise gas furnace

Advertisement

Indoor air is pernfitted for combustion, ventilation, and dilution,
if the Standard or Known-Air-Infiltration
Method is used,
CARBON
MONOXIDE
POISONING
HAZARD
Failure
to follow
this warning
could
result
in death
and/or
personal
injury.
Many
homes
require
air to be supplied
from
outdoors
for
furnace
combustion,
ventilation,
and dilution
of flue gases.
The
furnace
combustion
air supply
must
be provided
in
accordance
with this instruction
manual.
The Standard
Method:
1. The space has no less volume
than 50 cubic feet per 1,000
Btuh of the maximum
input
ratings
for all gas appliances
installed
in the space and
2. The air infiltration
rate is not known
to be less than 0.40
air changes
per hour (ACH).
The Known
Air Infiltration
Rate
Method
shall be used,
if the
infiltration
rate is known
to be:
1. Less than 0.40 ACH and
2. Equal to or greater
than 0.10 ACH
Infiltration
rates greater
than 0.60 ACH
shall not be used.
The
minimum
required
volume
of the space varies with the number
of
ACH and shall be deternfined
per Table 3 or Equations
1 and 2.
Deternfine
the minimum
required
volume
for each appliance
in
the space
and add the volumes
together
to get the total nfininmm
required
volume
for the space.
Table
3-Minimum
Space
Volumes
were
deternfined
by using
the following
equations
from the National
Fuel Gas Code ANSI
Z223.1-2009/NFPA
54-2009,
9.3.2.2:
1. For other than
fan-assisted
appliances,
such as a draft
hood-equipped
water heater:
Volume
- 21ft3 _
[ °ther
Other ACH
000 Btu/hr
2. For fan-assisted
appliances
such as this furnace:
Volume
_ 15ft 3 _
I fan
Fan
ACH
000 Btu/hr
A04002
A04003
If:
Iother = combined
input of all other than fan-assisted
appliances
in Btuh/hr
Ifan = combined
input of all fan-assisted
appliances
in Btuh/hr
ACH = air changes
per hour (ACH shall not exceed
0.60).
The following
requirements
apply to the Standard
Method
and to
the Known
Air Infiltration
Rate Method.
1. Adjoining
rooms
can be considered
part of a space if:
a. There are no closeable
doors between
rooms.
b. Combining
spaces
on same floor
level.
Each opening
shall have free area of at least 1 in.2/l,000
Btuh (2,000
mm2/kW)
of the total input rating of all gas appliances
in the space,
but not less than 100 in. 2 (0.06 m2). One
opening
shall commence
within
12-in.
(300 ram) of the
ceiling
and the second
opening
shall commence
within
12-in.
(300 ram) of the floor. The nfininmm
dimension
of air openings
shall be at least 3-in. (80 ram). (See Fig.
8.)
10
INTERIOR
HEATED
SPACE
1
1
I
I
CIRCULATING
AIR
DUCTS
I
I
II
I
I
VENT THROUGH
ROOF
:305mm)
1 SQ iN.
PER 1000
BTUH*
IN DOOR
OR WALL
UNCONFINED
SPACE
6" MIN (152mm)
(FRONT)0
CIRCULATING
AIR DUCTS
1 SQ IN.
PER 1000
BTUH*
IN DOOR
OR WALL
L 12" MAX (3O5mm)
* Minimum
opening
size is 100 sq in. (64516
sq, mm)with
minimum
dimensions
of 3 in. (76 mm)
1- Minimum
of 3 in. (76 mm) when
type-B1
vent
is used.
A03175
Fig. 8 - Air for Combustion,
Ventilation,
and Dilution
from
Indoors
c. Combining
space on different
floor levels. The volumes
of spaces
on different
floor levels shall be considered
as
communicating
spaces if connected
by one or more per-
manent
openings
in doors
or floors
having
free area of
at least 2 in.2/l,000
Btuh (4,400 mm2/kW)
of total input
rating of all gas appliances.
2. An
attic or crawlspace
may be considered
a space
that
freely conmmnicates
with the outdoors
provided
there are
adequate
permanent
ventilation
openings
directly
to out-
doors having
free area of at least 1 -in.2/4,000
Btuh of total
input rating for all gas appliances
in the space.
3. In spaces that use the Indoor Combustion
Air Method,in-
filtration
should
be adequate
to provide
air for combus-
tion,
permanent
ventilation
and
dilution
of flue
gases.
However,
in buildings
with
unusually
tight construction,
additional
air MUST
be provided
using the methods
de-
scribed
in the Outdoor
Combustion
Air Method
section.
Unusually
tight construction
is defined
as construction
with:
a. Walls and ceilings
exposed
to the outdoors
have a con-
tinuous,
sealed vapor barrier.
Openings
are gasketed
or
sealed and
b. Doors and openable
windows
are weatherstripped
and
c. Other
openings
are caulked
or sealed.
These
include
joints
around
window
and door frames,
between
sole
plates and floors, between
wall-ceiling
joints,
between
wall panels,
at penetrations
for plumbing,
electrical
and
gas lines, etc.
Combination
of Indoor
and Outdoor
Air
1. Indoor
openings
shall comply
with
the Indoor
Combus-
tion Air Method
below
and,

Advertisement

loading