ANSI Hardware Installation Manual
10
11
Procedure 57
Use the following procedure when the power cables need to be disconnected on 7360 ISAM FX-8.
1
2
3
4
5
14.6 CO alarm connector
Figure
Figure 140
Issue: 09
Verify that the fans spin.
STOP. This procedure is complete.
To disconnect the power cables
Warning — If the following sequence is not followed exactly, there can
be a possible fire hazard.
Before disconnecting the power cables, ensure that power to the cables has been
disconnected.
Switch off the circuit breakers for BAT A and BAT B
Disconnect the battery cables BAT A and BAT B
Disconnect the BATRET cables RET A and RET B
STOP. This procedure is complete.
140
shows the external interfaces on the 7360 ISAM FX-8 shelf.
External interfaces on 7360 ISAM FX-8
A-40A
External Alarms
3HH-12893-AAAA-TCZZA
7360 ISAM FX-8
NTA GND NTB
TOD/IHZ
Remote Craft
BITS
DRAFT
7360 ISAM FX-8 shelf cabling
Alarms
Critical
Major
Minor
BAT A
BAT B
ACO
21969
269