Actual Value Channels; Trip Line; Drive-Cliq Interface - Siemens SINAMICS SM150 Operating And Installation Instructions

Medium-voltage drive
Table of Contents

Advertisement

B.2.4.3

Actual value channels

Table B-16
Single fiber-optic cable
X70, X71
X72, X73
X74, X75
X76 to X78
X79
B.2.4.4

Trip line

Table B-17
Fiber-optic cable
X81
● Two PSAs Duplex fiber-
● > two PSAs Single fiber-
B.2.4.5

DRIVE-CLiQ interface

Table B-18
Pin
1
2
3
4
5
6
7
8
A
B
Blanking plate for DRIVE-CLiQ interface: Molex, order number: 85999-3255.
The maximum DRIVE-CLiQ cable length is 50 m.
SINAMICS SM150 6SL3845-7NN46-7AA0
Operating Instructions 04/2017
Power Stack Adapter 2: Actual value channels
Meaning, actual value acquisition
DC-link voltages
Output currents
Output voltages
N.C.
Voltage sensing braking chopper
Power Stack Adapter 2: Trip line
optic cable;
optic cable)
DRIVE-CLiQ interface
Signal name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
Meaning
Trip line for direct data ex‐
change between PSAs
Technical data and drawings
B.2 Terminal assignments
Technical specifications
Fiber-optic cable type: 2 mm
plastic optical fiber (POF)
Max. length of fiber-optic cable:
20 m
Technical data
Fiber-optic cable type:
2 mm plastic optical fiber (POF)
Max. length of fiber-optic cable: 10 m
Technical data
Transmit data +
Transmit data -
Receive data +
Receive data -
Power supply
Electronics ground
205

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents