Ng/Pv Dual Fuel System; Low Fuel Level Alarm; Gas Detector; Fluid Spill Alarm - Generac Power Systems SG30 Owner's Manual

Standby generator, tank set, natural gas, riser frame
Hide thumbs Also See for SG30:
Table of Contents

Advertisement

NG/PV DUAL FUEL SYSTEM

This system may be set up to run primarily on either
natural gas or propane vapor. When the primary fuel
pressure drops below 4 inches of water, the generator
switches to run on the secondary fuel.
This unit is shipped for operation on both natural
gas, and liquid propane vapor (propane) fuel. The
natural gas low pressure switch is programmed as
an alarm only and will not shut the unit down. The
propane fuel will take over supplying the engine auto-
matically.
If the unit is to be used solely for natural gas usage,
the low pressure switch needs to be programmed
as a shut down function by an Authorized Service
Dealer.

LOW FUEL LEVEL ALARM

This standby generator is equipped with a low fuel
level alarm when propane vapor is used. When the
fuel level in the propane tank gets low, an alarm will
sound to notify operator.
Standby Generator Sets
Fuel Systems

GAS DETECTOR

Either one or two gas detectors may be equipped on
this unit. They are located on the frame and detect if
there is a fuel leak. If the detector(s) senses a leak,
the unit will shut down.

FLUID SPILL ALARM

This alarm notifies the operator when there is a spill
inside the enclosure, i.e. coolant, oil.