System Operation
Figure 7-12. Enabling REbus Devices (3 of 3)
a. Notice there will be multiple pages of S2502 PV
Links. Watch the horizontal cursor at the top of each
page to indicate a new page. Press the center but-
ton on a device to reference its RCPn and confirm
the device ID.
11. See
Figure
7-13. Confirm PV Links are in state,
"making power."
a. See
Figure
7-14. If the PV Link goes directly to
"low sun," disable the device and select "Auto
Cfg PVRSS."
b. If the PV Link still goes directly to "low sun,"
contact the Independent Authorized Service
Dealer (IASD) who installed the system.
PV Link S2502
Photovoltaics
Making Power
Power:
PV Voltage:
E-total:
Figure 7-13. PV Link Device Page
PV Link S2502
Disable
Mod.
Settings
Auto Cfg PVRSS
RCPn: 00010003XXXX
< EXIT
SCROLL > NEXT • SELECT
Figure 7-14. PV Link - Auto Cfg PVRSS
12. Confirm PWRcell Batteries are in state "standby,"
"charging," or "discharging" (state will depend on
system mode selected).
52
NOTE: It is only necessary to enable the REbus Beacon
if setting the system to operate on a Time of Use (TOU)
schedule. See
Commissioning Steps

Confirm Inverter Settings

Once the system is activated, confirm the system mode,
and navigate to the inverter device page. Press the cen-
ter button to access the "Mod. Settings" menu for the
inverter, and confirm the settings are set correctly for the
system installed.
015179

PV Only System

-xx
0W
115v
59.0kWh
013439
Menu
PV + Battery w / a Protected Loads Subpanel for
Partial Home Backup
013437
Installation and Owner's Manual for Generac PWRCell Inverter
Section 6:
Commissioning Advanced
for more information.
– System mode should be "Grid Tie."
– See
Figure 7-15
and
Settings:"
o 'EnaIslanding' should be 'off.'
o All other settings should be at their default
values.
PWRcell 2P Inv.
Disable
Mod. Settings
Calibrate CTs
RCPn: 000100073212
< EXIT
SCROLL > NEXT • SELECT
Figure 7-15. PV Only System (1 of 2)
TargMinImprtP
Enalslanding
NumTranSwtchs
ExTransVolt
Cancel
Figure 7-16. PV Only System (2 of 2)
– System mode should be Self Supply, Clean
Backup, or Priority Backup.
– See
and
Figure 7-17
Settings:"
o 'EnaIslanding' should be 'on.'
o All other settings should be at their default
values.
Figure
7-16. Inverter "Mod.
Menu
013436
0
off
0
95
Save
013438
7-18. Inverter "Mod.
Figure