Unit Placement - Lennox XP16 Series Unit Information

Hfc-410a
Table of Contents

Advertisement

CLEARANCE ON ALL SIDES
6 (152)
12 (305)
36 (914)
MINIMUM CLEARANCE BETWEEN
TWO UNITS

Unit Placement

CAUTION
In order to avoid injury, take proper precaution when lifting
heavy objects.
See Unit Dimensions on page 3 for sizing mounting slab,
platforms or supports. Refer to figure 5 for mandatory
installation clearance requirements.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
D
Some localities are adopting sound ordinances based
on the unit's sound level registered from the adjacent
property, not from the installation property. Install the
unit as far as possible from the property line.
When possible, do not install the unit directly outside a
D
window. Glass has a very high level of sound
transmission. For proper placement of unit in relation to
a window see the provided illustration in figure 6, detail
A.
INCHES (MILLIMETERS)
ACCESS PANEL
NOTES:
CONTROL PANEL
D
ACCESS
LOCATION
30 (762)
D
LINE SET
CONNECTIONS
24 (610)
Figure 5. Installation Clearances
Clearance to one of the other three
sides must be 36 inches (914mm).
Clearance to one of the remaining
two sides may be 12 inches
(305mm) and the final side may be
6 inches (152mm).
PLACING UNIT ON SLAB
When installing unit at grade level, the top of the slab should
be high enough above grade so that water from higher
ground will not collect around the unit. The slab should have
a slope tolerance as described in figure 6, detail B.
NOTE
If necessary for stability, anchor unit to slab as
described in figure 6, detail D.
ELEVATING THE UNIT
Units are outfitted with elongated support feet as illustrated
in figure 6, detail C.
If additional elevation is necessary, raise the unit by
extending the height of the unit support feet. This may be
achieved by using a 2 inch (50.8mm) Schedule 40 female
threaded adapter.
The specified coupling will fit snuggly into the recessed
portion of the feet. Use additional 2 inch (50.8mm) Schedule
40 male threaded adaptors which can be threaded into the
female threaded adaptors to make additional adjustments to
the level of the unit.
NOTE
Keep the height of extenders short enough to
ensure a sturdy installation. If it is necessary to extend
further, consider a different type of field−fabricated
framework that is sturdy enough for greater heights.
Page 10
MINIMUM CLEARANCE
ABOVE UNIT
48 (1219)
XP16